Table 3.12 - Ac Input Line Fuse Selection Values - Reliance electric 2V4160 Hardware Installation And Troubleshooting Manual

Ac drive
Table of Contents

Advertisement

*Recommended fuse type: UL Class J, 600 V, time delay, or equivalent.
**The drive contains internal fusing sized to protect the drive. Install fuses to protect the input wiring in
3-10
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Table 3.12 – AC Input Line Fuse Selection Values
Drive
Model Number
1V4160 1V4460
2V4160 2V4460
3V4160 3V4460
5V4160 5V4460
7V4160 7V4260
10V4160 10V4260
15V4160 15V4260
20V4160 20V4260
25G4160 25G4260
25V4160 25V4260
30V4160 30V4260
40V4160 40V4260
50V4160 50V4260
50R4160 50T4160
60G4160 60G4260
75R4160 75T4160
125R4160
200V4160
250V4160
300V4160
350V4160
400V4160
accordance with local codes.
Selected Regulation
and
Horsepower Rating
V/Hz or Vector (1 HP)
V/Hz or Vector (2 HP)
V/Hz or Vector (3 HP)
V/Hz or Vector (5 HP)
V/Hz or Vector (7.5 HP)
V/Hz or Vector (10 HP)
V/Hz or Vector (15 HP)
V/Hz or Vector (20 HP)
V/Hz (25 HP)
V/Hz or Vector (25 HP)
V/Hz or Vector (30 HP)
V/Hz or Vector (40 HP)
V/Hz or Vector (50 HP)
Vector (50 HP) or
V/Hz (75 HP)
V/Hz (60 HP)
Vector (60-75 HP) or
V/Hz (100 HP)
Vector (100-125 HP) or
V/Hz (125-150 HP)
Vector (150-200 HP) or
V/Hz (200 HP)
V/Hz or Vector (250 HP)
V/Hz or Vector (300 HP)
V/Hz or Vector (350 HP)
V/Hz or Vector (400 HP)
GV3000/SE AC Drive Hardware Reference, Version 6.06
Input Voltage
Fuse
(+/-10%)
Rating*
380-460 VAC
6 A
380-460 VAC
8 A
380-460 VAC
12 A
380-460 VAC
20 A
380-460 VAC
25 A
380-460 VAC
35 A
380-460 VAC
45 A
380-460 VAC
60 A
380-460 VAC
70 A
380-460 VAC
70 A
380-460 VAC
100 A
380-460 VAC
100 A
380-460 VAC
125 A
380-460 VAC
125 A
380-460 VAC
150 A
380-460 VAC
125 A
150 A
380-460 VAC
250 A
380-460 VAC
**
380-460 VAC
**
380-460 VAC
**
380-460 VAC
**
380-460 VAC
**

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gv3000se5v4160Gv300088490-188490-288490-3

Table of Contents