Using Socket Services with Socket Service Request Switches
UDP Socket Close Request
TCP Socket Passive Open Request
Response
code
110C
Request Switch turned ON during other processing.
220F
Specified socket is already processing a send request.
2210
The specified socket is not open.
2211
Unit is busy; cannot execute.
2607
Specified Socket Service Parameter Area is already being used for
another socket.
003E
Internal buffer cannot be obtained due to high reception traffic
(ENOBUFS).
0042
The remote IP address is a broadcast address and the number of
bytes to send is greater than 1,472 bytes (EMSGSIZE).
004C
The network ID is incorrect or the remote IP address is incorrect
(EADDRNOTAVAIL)
004E
The network ID is not in the IP router table, router settings are incor-
rect, or the remote IP address is incorrect (ENETUNREACH).
0051
The router settings are incorrect or the remote IP address is incor-
rect (EHOSTUNREACH).
0081
The specified socket was closed during send processing.
Response
code
0000
Normal end
0302
CPU Unit error; cannot execute.
2210
The specified socket is not open.
2211
Unit is busy; cannot execute.
2607
Specified Socket Service Parameter Area is already being used for
another socket.
Response
code
0000
Normal end
0105
Local IP address setting error.
0302
CPU Unit error; cannot execute.
1100
TCP socket number is not 1 to 8 or local TCP port number is 0.
110C
Request Switch turned ON during other processing.
220F
Specified socket is already open or already processing an open
request.
2211
Unit is busy; cannot execute.
2606
Specified socket is already open as UDP socket; cannot open TCP
socket.
2607
Specified Socket Service Parameter Area is already being used for
another socket.
003E
Internal buffer cannot be obtained due to high reception traffic
(ENOBUFS).
0042
The remote IP address is a broadcast address and the number of
(See note.)
bytes to send is greater than 1,472 bytes (EMSGSIZE).
0045
Error in communications with remote node (ECONNABORTED).
0049
The same TCP port number has been specified more than once
(EADDRINUSE).
004A
Error (ECONNREFUSED).
(See note.)