Omron CS1W-ETN11 Operation Manual page 112

10base-5, 10base-t ethernet units
Hide thumbs Also See for CS1W-ETN11:
Table of Contents

Advertisement

Sending Commands From a PC
Timing of Communications Flag Changes
Example
Communications Port Enabled Flag
Communications instruction:
SEND(090), RECV(098), CMND(490)
Communications Port Error Flag
Communications Port Completion Code
Communications Port Error Flag and Completion Codes CMND(490)
Errors that occur when CMND(490) is used generate a Communications Port
Error Flag and are recorded in a communications port completion code only in
the following cases:
• When a response timeout error has occurred.
• When the number of communications data bytes exceeds the maximum
value for the Unit (i.e., 2,000 bytes for the Ethernet Unit).
• When the actual number of response bytes is greater than the number of
reception bytes that has been set. (The response is not stored in this
case.)
Errors other than these are recorded in the response codes of the responses
stored from the beginning response storage word onwards. Be careful of
these, because there are no Communications Port Error Flags and they are
not recorded in a communications port completion code.
• The Communications Port Enabled Flag remains OFF during communica-
tions and turns ON when they are completed (regardless of whether or
not an error occurs).
• The Communications Port Error Flag retains its status until the next trans-
mission or reception.
• The Communications Port Error Flag turns OFF with the execution of the
next communications instruction even if there was an abnormal comple-
tion.
Instruction 1
being executed.
Completion
0000 (Normal completion)
Instruction 2
Instruction 3
being executed.
being executed.
0000 (Normal completion)
(Unit address setting error)
Section 5-3
91