7. Analog and Digital Input Configurations
7.1.
Terminal Mode (P-12 = 0)
P-15
Digital input 1 (T2)
Open: Stop (disable)
0
Closed: Run (enable)
Open: Stop (disable)
1
Closed: Run (enable)
Open: Stop (disable)
2
Closed: Run (enable)
Open: Stop (disable)
3
Closed: Run (enable)
Open: Stop (disable)
4
Closed: Run (enable)
Open: Fwd Stop
5
Closed: Fwd Run
Open: Stop (disable)
6
Closed: Run (enable)
Open: Stop (disable)
7
Closed: Fwd Run (enable)
Open: Stop (disable)
8
Closed: Run (enable)
Open: Stop (disable)
9
Closed: Forward Run
(enable)
Normally Open (NO)
10
Momentary close to run
Normally Open (NO)
11
Momentary close to run
Open: Stop (disable)
12
Closed: Run (enable)
NOTE
Negative Preset Speeds will be inverted if Run Reverse selected
Typical Applications
Terminal Mode P-12=0, P-15=0
+24 Volt
Run (Enable)
For / Rev
Analog / Preset
+ 10 Volts
Reference
0 Volts
Analog speed input with 1 preset speed and
fwd/rev switch
22
Optidrive ODE-2 User Guide Revision 3.20
Digital input 2 (T3)
Digital input 3 (T4)
Open : Forward run
Open : Analog speed ref
Closed : Reverse run
Closed : Preset speed 1
Open: Analog speed ref
Open: Preset speed 1
Closed : Preset speed 1/2
Closed : Preset speed 2
Digital Input 2
Digital Input 3
Open
Open
Closed
Open
Open
Closed
Closed
Closed
External trip input :
Open : Analog speed ref
Open: Trip,
Closed : Preset speed 1
Closed: Run
Open : Analog input 1
Analog input 2 reference Analog input 1 reference
Closed : Analog input 2
Open: Reverse Stop
Open : Analog speed ref
Closed: Reverse Run
Closed : Preset speed 1
External trip input :
Open : Forward
Open: Trip,
Closed : Reverse
Closed: Run
External trip input :
Open: Stop (disable)
Open: Trip,
Closed: Rev Run (enable)
Closed: Run
Digital Input 3
Open
Open : Forward
Closed
Closed : Reverse
Open
Closed
Digital Input 3
Open
Open: Stop (disable)
Closed: Reverse Run
Closed
(enable)
Open
Closed
Normally Closed (NC)
Open : Analog speed ref
Momentary open to stop
Closed:Preset speed 1
Normally Closed (NC)
Normally Open (NO)
Momentary open to stop
Momentary close to rev
Open: Fast Stop (disable)
Open : Analog speed ref
Closed: Run (enable)
Closed : Preset speed 1
Terminal Mode P-12=0, P-15 = 1
Analog speed input with 2 preset speeds
www.invertekdrives.com
Analog input (T6)
Analog input 1 reference
Analog input 1 reference
Preset Speed
Preset Speed 1
Open: Preset speeds 1-4
Preset Speed 2
Closed : Max Speed(P-01)
Preset Speed 3
Preset Speed 4
Analog input 1 reference
Analog input 1 reference
Analog input 1 reference
Analog input 1 reference
Analog Input 1
Preset Speed
Open
Preset Speed 1
Open
Preset Speed 2
Closed
Preset Speed 3
Closed
Preset Speed 4
Analog Input 1
Preset Speed
Open
Preset Speed 1
Open
Preset Speed 2
Closed
Preset Speed 3
Closed
Preset Speed 4
Analog input 1 reference
Analog input 1 reference
Analog input 1 reference
+24 Volt
Run (Enable)
Analog / Preset
Preset1 / Preset2
+ 10 Volts
Reference
0 Volts
4 preset speeds and max speed select switch.
Comments
4 Preset speeds selectable.
Analog input used as digital
input Closed status: 8V < Vin
< 30V
Connect external motor
thermistor PTC type or
similar to digital input 3
Switches between analog
inputs 1 and 2
Closing digital inputs 1 and 2
together carries out a fast
stop (P-24)
Connect external motor
thermistor PTC type or
similar to digital input 3
Closing digital inputs 1 and 2
together carries out a fast
stop (P-24)
Closing digital inputs 1 and 2
together carries out a fast
stop (P-24)
Closing digital inputs 1 and 3
together carries out a fast
stop (P-24)
Terminal Mode P-12=0, P-15=2
+24 Volt
Run (Enable)
Preset Speeds 1 – 4
Select
Preset / Max
Effectively giving 5 preset speeds