4.9.
Using the REV/0/FWD Selector Switch (Switched Version Only)
By adjusting the parameter settings the Optidrive can be configured for multiple applications and not just for Forward or Reverse.
This could typically be for Hand/Off/Auto applications (also known and Local/Remote) for HVAC and pumping industries.
Switch Position
Run Reverse
STOP
Preset Speed 1
Run Reverse
Run in Auto
Run in Speed Control
Run in Preset Speed
Control
Run in Hand
Run in Hand
NOTE
To be able to adjust parameter P-15, extended menu access must be set in P-14 (default value is 101)
4.10. Control Terminal Connections
Default Connections
Optidrive ODE-2 User Guide Revision 3.20
STOP
Run Forward
STOP
Run Forward
STOP
Run Forward
STOP
Run Forward
STOP
Run in Hand
STOP
Run in PI Control
STOP
Run in PI Control
STOP
Run in Auto
STOP
Run in Auto
Control
Signal
Terminal
1
+24V User Output,
2
Digital Input 1
3
Digital Input 2
Digital Input 3 /
4
Analog Input 2
5
+10V User Output
Analog Input 1 /
6
Digital Input 4
7
Analog Output /
8
Digital Output
9
10
Relay Common
11
Relay NO Contact
www.invertekdrives.com
Parameters to Set
P-12
P-15
0
0
0
5,7
0
1
0
6, 8
0
4
5
1
0, 2, 4,5,
5
8..12
3
6
3
3
Description
+24V, 100mA.
Positive logic
"Logic 1" input voltage range: 8V ... 30V DC
"Logic 0" input voltage range: 0V ... 4V DC
Digital: 8 to 30V
Analog: 0 to 10V, 0 to 20mA or 4 to 20mA
+10V, 10mA, 1kΩ minimum
Analog: 0 to 10V, 0 to 20mA or 4 to 20mA
Digital: 8 to 30V
0V
User ground connected terminal 9
Analog: 0 to 10V,
Digital: 0 to 24V
0V
User ground connected terminal 7
Contact 250Vac, 6A / 30Vdc, 5A
Notes
Factory Default Configuration
Run Forward or Reverse with speed controlled from the
Local POT
Run forward with speed controlled form the local POT
Run Reverse - disabled
Run Forward with speed controlled from the Local POT
Preset Speed 1 provides a 'Jog' Speed set in P-20
Run Forward or Reverse with speed controlled from the
Local POT
Run in Hand – Speed controlled from the Local POT
Run in Auto 0 Speed controlled using Analog input 2 e.g.
from PLC with 4-20mA signal.
In Speed Control the speed is controlled from the Local
POT
In PI Control, Local POT controls PI set point
In Preset Speed Control, P-20 sets the Preset Speed
In PI Control, POT can control the PI set point
(P-44=1)
Hand – speed controlled from the Local POT
Auto – Speed Reference from Modbus
Hand – Speed reference from Preset Speed 1 (P-20)
Auto – Speed Reference from Modbus
20mA maximum
15