Code
[4.5]
[F-0D]
▪ 1 Sample: The pump is ON when
there is heating or cooling demand as
the leaving water temperature has not
yet reached the desired temperature
yet. When thermo OFF condition
occurs, the pump runs every 3 minutes
to check the water temperature and
demand
necessary. Remark: Sample is ONLY
available in leaving water temperature
control.
a
b
d
g
b
▪ a: Space heating/cooling control
▪ b: Off
▪ c: On
▪ d: LWT temperature
▪ e: Actual
▪ f: Desired
▪ g: Pump operation
[4.5]
[F-0D]
▪ 2 Request: Pump operation based on
request. Example:
thermostat and thermostat creates
thermo ON/OFF condition. Remark:
NOT
temperature control.
a
b
d
e
b
▪ a: Space heating/cooling control
▪ b: Off
▪ c: On
▪ d: Heating demand (by external
▪ e: Pump operation
Unit type
In this part of the menu it can be read out which type of unit is used:
#
Code
[4.6]
[E‑02]
Unit type:
▪ 0 Reversible (only with EKHVCONV2
installed)
▪ 1 Heating only
Pump limitation
The pump speed limitation for the main zone [9‑0E] and additional
zone [9‑0D] defines the maximum pump speed. In normal
conditions, the default setting should NOT be modified. The pump
speed limitation will be overruled when the flow rate is in the range
of the minimum flow (error 7H).
EPGA11~16DAV3 + EAVZ16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556075-1 – 2019.02
Description
heating
or
cooling
c
e
f
c
Using a room
available
in
leaving
water
c
c
b
c
room
thermostat
or
room
thermostat)
Description
#
Code
[4.7]
[9-0D]
if
[4.8]
[9-0E]
The maximum values depend on the unit type:
[9-0D]=0
a (kPa)
b (l/min)
[9-0D]=6
a (kPa)
b (l/min)
8 Configuration
Description
Pump limitation Additional zone:
▪ 0: No limitation
▪ 1~4: General limitation. There is
limitation
in
all
conditions.
required delta T control and comfort
are NOT guaranteed.
▪ 5~8: Limitation when no actuators.
When there is no heating output, the
pump speed limitation is applicable.
When there is heating output, the
pump speed is only determined by
delta  T in relation to the required
capacity. With this limitation range,
delta  T is possible and the comfort is
guaranteed.
Pump limitation Main zone:
▪ 0: No limitation
▪ 1~4: General limitation. There is
limitation
in
all
conditions.
required delta T control and comfort
are NOT guaranteed.
▪ 5~8: Limitation when no actuators.
When there is no heating output, the
pump speed limitation is applicable.
When there is heating output, the
pump speed is only determined by
delta  T in relation to the required
capacity. With this limitation range,
delta  T is possible and the comfort is
guaranteed.
[9-0D]=5
a (kPa)
[9-0D]=7
a (kPa)
Installer reference guide
The
The
b (l/min)
b (l/min)
51