Daikin Altherma EPGA16DAV3 Installer's Reference Manual page 95

Low temperature split
Hide thumbs Also See for Altherma EPGA16DAV3:
Table of Contents

Advertisement

8/10
Field settings table
Breadcrumb
Field code
Setting name
9.I
[5-03]
Space heating priority temperature.
9.I
[5-04]
Set point correction for domestic hot water temperature.
9.I
[5-05]
What is the requested limit for DI1?
9.I
[5-06]
What is the requested limit for DI2?
9.I
[5-07]
What is the requested limit for DI3?
9.I
[5-08]
What is the requested limit for DI4?
9.I
[5-09]
What is the requested limit for DI1?
9.I
[5-0A]
What is the requested limit for DI2?
9.I
[5-0B]
What is the requested limit for DI3?
9.I
[5-0C]
What is the requested limit for DI4?
9.I
[5-0D]
Backup heater voltage
9.I
[5-0E]
--
9.I
[6-00]
The temperature difference determining the heat pump ON temperature.
9.I
[6-01]
The temperature difference determining the heat pump OFF temperature.
9.I
[6-02]
What is the capacity of the booster heater?
9.I
[6-03]
What is the capacity of the backup heater step 1?
9.I
[6-04]
What is the capacity of the backup heater step 2?
9.I
[6-05]
--
9.I
[6-06]
--
9.I
[6-07]
--
9.I
[6-08]
What is the hysteresis to be used in reheat mode?
9.I
[6-09]
--
9.I
[6-0A]
What is the desired comfort storage temperature?
9.I
[6-0B]
What is the desired eco storage temperature?
9.I
[6-0C]
What is the desired reheat temperature?
9.I
[6-0D]
What is the desired DHW production type?
9.I
[6-0E]
What is the maximum temperature setpoint?
9.I
[7-00]
Domestic hot water booster heater overshoot temperature.
9.I
[7-01]
Domestic hot water booster heater hysteresis.
9.I
[7-02]
How many leaving water temperature zones are there?
9.I
[7-03]
--
9.I
[7-04]
--
9.I
[7-05]
Boiler efficiency
9.I
[8-00]
Minimum running time for domestic hot water operation.
9.I
[8-01]
Maximum running time for domestic hot water operation.
9.I
[8-02]
Anti-recycling time.
9.I
[8-03]
Booster heater delay timer.
9.I
[8-04]
Additional running time for the maximum running time.
9.I
[8-05]
Allow modulation of the LWT to control the room temp?
9.I
[8-06]
Leaving water temperature maximum modulation.
9.I
[8-07]
What is the desired comfort main LWT in cooling?
9.I
[8-08]
What is the desired eco main LWT in cooling?
9.I
[8-09]
What is the desired comfort main LWT in heating?
9.I
[8-0A]
What is the desired eco main LWT in heating?
9.I
[8-0B]
--
9.I
[8-0C]
--
9.I
[8-0D]
--
9.I
[9-00]
What is the maximum desired LWT for main zone in heating?
9.I
[9-01]
What is the mimimum desired LWT for main zone in heating?
9.I
[9-02]
What is the maximum desired LWT for main zone in cooling?
4P556077-1 - 2018.12
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W (*1)
R/O (*2)
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/O
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
(#) Setting is not applicable for this unit.
Range, step
Default value
-15~35°C, step: 1°C
0°C
0~20°C, step: 1°C
10°C
0~50 A, step: 1 A
50 A
0~50 A, step: 1 A
50 A
0~50 A, step: 1 A
50 A
0~50 A, step: 1 A
50 A
0~20 kW, step: 0,5 kW
20 kW
0~20 kW, step: 0,5 kW
20 kW
0~20 kW, step: 0,5 kW
20 kW
0~20 kW, step: 0,5 kW
20 kW
0: 230V, 1~ (*1)
1: 230V, 3~ (*1)
2: 400V, 3~ (*2)
1
2~40°C, step: 1°C
28°C (*4)
22°C (*5)
0~10°C, step: 1°C
2°C
0~10kW, step: 0,2kW
0kW
0~10kW, step: 0,2kW
2kW (*1)
3kW (*2)
0~10kW, step: 0,2kW
4kW (*1)
6kW (*2)
0
0
0
2~20°C, step: 1°C
10°C
0
30~[6-0E]°C, step: 1°C
60°C
30~min(50, [6-0E])°C, step: 1°C
45°C
30~min(50, [6-0E])°C, step: 1°C
45°C
0: Reheat only
1: Reheat + sched.
2: Scheduled only
40~60°C, step: 1°C
60°C
0~4°C, step: 1°C
0°C
2~40°C, step: 1°C
2°C
0: 1 LWT zone
1: 2 LWT zones
2.5
0
0: Very high
1: High
2: Medium
3: Low
4: Very low
0~20 min, step 1 min
1 min
5~95 min, step: 5 min
30 min
0~10 hour, step: 0,5 hour
0,5 hour
20~95 min, step: 5 min
50 min
0~95 min, step: 5 min
95 min
0: No
1: Yes
0~10°C, step: 1°C
5°C
[9-03]~[9-02], step: 1°C
18°C (*3)
[9-03]~[9-02], step: 1°C
20°C (*3)
[9-01]~[9-00], step: 1°C
35°C
[9-01]~[9-00], step: 1°C
33°C
13
10
16
[2-0C]=2:
37~60, step: 1°C
55°C
[2-0C]≠2:
37~55, step: 1°C
55°C
15~37°C, step: 1°C
25°C
18~22°C, step: 1°C
22°C (*3)
(*4) EAVZ16S18*_(*5) EAVZ16S23*
Installer setting at variance with
default value
Date
Value
(*1) *6V_(*2) *9W_
(*3) + EKHVCONV2_