8 Configuration
Heating WD curve
Set weather-dependent heating for the main zone (if [2.4] = 1 or 2):
#
Code
[2.5]
[1-00]
Set weather-dependent heating:
T t
[1-01]
[1-02]
[1-02]
[1-03]
[1-03]
▪ T
: Target leaving water temperature
t
(main zone)
▪ T
: Outdoor temperature
a
▪ [1-00]:
temperature. –40°C~+5°C
▪ [1-01]:
temperature. 10°C~25°C
▪ [1-02]:
temperature
temperature equals or drops below the
low
[9‑01]°C~[9‑00]°C
Note: This value should be higher
than
temperatures
required.
▪ [1-03]:
temperature
temperature equals or rises above the
high
[9‑01]°C~min(45, [9‑00])°C
Note: This value should be lower than
[1‑02]
temperatures less warm water is
required.
Cooling WD curve
Set weather-dependent cooling for the main zone (if [2.4] = 2):
Installer reference guide
44
Description
[1-00]
[1-01]
T a
Low
outdoor
ambient
High
outdoor
ambient
Desired
leaving
water
when
the
outdoor
ambient
temperature.
[1‑03]
as
for
low
outdoor
warmer
water
is
Desired
leaving
water
when
the
outdoor
ambient
temperature.
as
for
high
outdoor
#
Code
[2.6]
[1-06]
Set weather-dependent cooling:
T t
[1-07]
[1-08]
[1-08]
[1-09]
[1-09]
▪ T
: Target leaving water temperature
t
(main zone)
▪ T
: Outdoor temperature
a
▪ [1-06]:
temperature. 10°C~25°C
▪ [1-07]:
temperature. 25°C~43°C
▪ [1-08]:
temperature
temperature equals or drops below the
low
[9‑03]°C~[9‑02]°C
Note: This value should be higher
than
temperatures
required.
▪ [1-09]:
temperature
temperature equals or rises above the
high
[9‑03]°C~[9-02]°C
Note: This value should be lower than
[1‑08]
temperatures colder water is required.
Emitter type
Depending on the system water volume and the heater emitter type
of the main zone, the heat up or cooling down of the main zone can
take longer. This setting can compensate for a slow or a quick
heating/cooling system during the heat up/cool down cycle (cooling
only with EKHVCONV2 installed).
The target delta T for the main zone will depend on this setting.
Target delta T control is only possible in case only 1 zone is active.
Pump control will be different when both zones are active.
In room thermostat control, this setting will influence:
▪ the
maximum
modulation
temperature.
▪ the possibility for usage of the automatic cooling/heating
changeover based on the indoor ambient temperature (only with
EKHVCONV2 installed).
Therefore it is important to set this correctly and in accordance with
your system layout.
#
Code
[2.7]
[2‑0C]
Emitter type
▪ 0: Underfloor heating
▪ 1: Fancoil unit
▪ 2: Radiator
The setting of the emitter type has an influence on the space heating
setpoint range and the target delta T in heating as follows:
EPGA11~16DAV3 + EAVZ16S18+23DA6V+9W
Description
[1-06]
[1-07]
Low
outdoor
ambient
High
outdoor
ambient
Desired
leaving
water
when
the
outdoor
ambient
temperature.
[1‑09]
as
for
low
outdoor
less
cold
water
Desired
leaving
water
when
the
outdoor
ambient
temperature.
as
for
high
outdoor
of
the
desired
leaving
water
Description
Daikin Altherma – Low temperature split
4P556075-1 – 2019.02