Daikin Altherma EPGA16DAV3 Installer's Reference Manual page 94

Low temperature split
Hide thumbs Also See for Altherma EPGA16DAV3:
Table of Contents

Advertisement

Field settings table
Breadcrumb
Field code
Setting name
9.I
[1-07]
High ambient temp. for LWT main zone cooling WD curve.
9.I
[1-08]
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
9.I
[1-09]
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
9.I
[1-0A]
What is the averaging time for the outdoor temp?
9.I
[1-0B]
What is the desired delta T in heating for the main zone?
9.I
[1-0C]
What is the desired delta T in heating for the additional zone?
9.I
[1-0D]
What is the desired delta T in cooling for the main zone?
9.I
[1-0E]
What is the desired delta T in cooling for the additional zone?
9.I
[2-00]
When should the disinfection function be executed?
9.I
[2-01]
Should the disinfection function be executed?
9.I
[2-02]
When should the disinfection function start?
9.I
[2-03]
What is the disinfection target temperature?
9.I
[2-04]
How long must the tank temperature be maintained?
9.I
[2-05]
Room antifrost temperature
9.I
[2-06]
Room frost protection
9.I
[2-09]
Adjust the offset on the measured room temperature
9.I
[2-0A]
Adjust the offset on the measured room temperature
9.I
[2-0B]
What is the required offset on the measured outdoor temp.?
9.I
[2-0C]
What emitter type is connected to the main LWT zone?
9.I
[2-0D]
What emitter type is connected to the additional LWT zone?
9.I
[2-0E]
What is the maximum allowed current over the heatpump ?
9.I
[3-00]
Is auto restart of the unit allowed?
9.I
[3-01]
--
9.I
[3-02]
--
9.I
[3-03]
--
9.I
[3-04]
--
9.I
[3-05]
--
9.I
[3-06]
What is the maximum desired room temperature in heating?
9.I
[3-07]
What is the mimimum desired room temperature in heating?
9.I
[3-08]
What is the maximum desired room temperature in cooling?
9.I
[3-09]
What is the minimum desired room temperature in cooling?
9.I
[4-00]
What is the BUH operation mode?
9.I
[4-01]
Which electric heater has priority?
9.I
[4-02]
Below which outdoor temperature is heating allowed?
9.I
[4-03]
Operation permission of the booster heater.
9.I
[4-04]
Water pipe freeze prevention
9.I
[4-05]
--
9.I
[4-06]
Emergency
9.I
[4-08]
Which power limitation mode is required on the system?
9.I
[4-09]
Which power limitation type is required?
9.I
[4-0A]
Backup heater configuration
9.I
[4-0B]
Automatic cooling/heating changeover hysteresis.
9.I
[4-0D]
Automatic cooling/heating changeover offset.
9.I
[5-00]
Is backup heater operation allowed above equilibrium temperature during space
heating operation?
9.I
[5-01]
What is the equilibrium temperature for the building?
9.I
[5-02]
Space heating priority.
(*1) *6V_(*2) *9W_
(*3) + EKHVCONV2_
(*4) EAVZ16S18*_(*5) EAVZ16S23*
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/O
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
(#) Setting is not applicable for this unit.
Range, step
Default value
25~43°C, step: 1°C
35°C (*3)
[9-03]~[9-02]°C, step: 1°C
22°C (*3)
[9-03]~[9-02]°C, step: 1°C
18°C (*3)
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
3~10°C, step: 1°C
5°C
3~10°C, step: 1°C
5°C
3~10°C, step: 1°C
5°C (*3)
3~10°C, step: 1°C
5°C (*3)
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
0: No
1: Yes
0~23 hour, step: 1 hour
1
60°C
40~60 min, step: 5 min
40 min
4~16°C, step: 1°C
8°C (*3)
0: Disabled
1: Enabled
-5~5°C, step: 0,5°C
0°C
-5~5°C, step: 0,5°C
0°C
-5~5°C, step: 0,5°C
0°C
0: Underfloor heating
1: Fancoil unit
2: Radiator
0: Underfloor heating
1: Fancoil unit
2: Radiator
20~50 A, step: 1 A
50 A
0: No
1: Yes
0
1
4
2
1
18~30°C, step: 0,5°C
30°C
12~18°C, step: 0,5°C
12°C
25~35°C, step: 0,5°C
35°C (*3)
15~25°C, step: 0,5°C
15°C (*3)
0: Disabled
1: Enabled
2: Only DHW
0: None
1: BSH
2: BUH
14~35°C, step: 1°C
35°C
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Legionella only
0: Intermittent
0
0: Manual
1: Automatic
0: No limitation
1: Continuous
2: Digital inputs
0: Current
1: Power
1: 1/1+2 (*1) (*2)
2: 1/2
3: 1/2 + 1/1+2 in emergency
1~10°C, step: 0,5°C
1°C (*3)
1~10°C, step: 0,5°C
3°C (*3)
0: Allowed
1: Not allowed
-15~35°C, step: 1°C
0°C
0: Disabled
1: Enabled
7/10
Installer setting at variance with
default value
Date
Value
4P556077-1 - 2018.12