Daikin Altherma EPGA16DAV3 Installer's Reference Manual page 92

Low temperature split
Hide thumbs Also See for Altherma EPGA16DAV3:
Table of Contents

Advertisement

Field settings table
Breadcrumb
Field code
Setting name
9.1
[0-03]
Low ambient temp. for LWT add zone heating WD curve.
9.1
[0-04]
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
9.1
[0-05]
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
9.1
[0-06]
High ambient temp. for LWT add zone cooling WD curve.
9.1
[0-07]
Low ambient temp. for LWT add zone cooling WD curve.
└─ Tank
9.1
[6-0D]
Heat up mode
9.1
[6-0A]
Comfort setpoint
9.1
[6-0B]
Eco setpoint
9.1
[6-0C]
Reheat setpoint
└─ Domestic hot water
9.2.1
[E-05]
Domestic hot water
[E-06]
[E-07]
9.2.2
[D-02]
DHW pump
9.2.4
[D-07]
Solar
└─ Back up heater
9.3.1
[E-03]
BUH type
9.3.2
[5-0D]
Voltage
9.3.3
[4-0A]
Configuration
9.3.4
[6-03]
Capacity step 1
9.3.5
[6-04]
Additional capacity step 2
9.3.6
[5-00]
Equilibrium
9.3.7
[5-01]
Equilibrium temperature
9.3.8
[4-00]
Operation
└─ Booster heater
9.4.1
[6-02]
Capacity
9.4.3
[8-03]
BSH eco timer
9.4.4
[4-03]
Operation
Installer settings
9.5
[4-06]
Emergency
└─ Balancing
9.6.1
[5-02]
Space heating priority
9.6.2
[5-03]
Priority temperature
9.6.3
[5-04]
Offset BSH setpoint
9.6.4
[8-02]
Anti-recycle timer
9.6.5
[8-00]
Minimum running timer
9.6.6
[8-01]
Maximum running timer
9.6.7
[8-04]
Additional timer
Installer settings
9.7
[4-04]
Water pipe freeze prevention
└─ Benefit kWh power supply
9.8.1
[D-01]
Benefit kWh power supply
9.8.2
[D-00]
Allow heater
9.8.3
[D-05]
Allow pump
└─ Power consumption control
9.9.1
[4-08]
Power consumption control
9.9.2
[4-09]
Type
9.9.3
[5-05]
Limit
9.9.4
[5-05]
Limit 1
(*1) *6V_(*2) *9W_
(*3) + EKHVCONV2_
(*4) EAVZ16S18*_(*5) EAVZ16S23*
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/O
R/W
R/W
R/O
R/W (*1)
R/O (*2)
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/O
R/W
R/W
R/O
R/W
R/W
R/W
R/W
R/W
R/W
R/W
(#) Setting is not applicable for this unit.
Range, step
Default value
-40~5°C, step: 1°C
-10°C
[9-07]~[9-08]°C, step: 1°C
8°C (*3)
[9-07]~[9-08]°C, step: 1°C
12°C (*3)
25~43°C, step: 1°C
35°C (*3)
10~25°C, step: 1°C
20°C (*3)
0: Reheat only
1: Reheat + sched.
2: Scheduled only
30~[6-0E]°C, step: 1°C
60°C
30~min(50, [6-0E])°C, step: 1°C
45°C
30~min(50, [6-0E])°C, step: 1°C
45°C
3: Integrated
0: No
1: Secondary rtrn
2: Disinf. Shunt
0: No
1: Yes
3: 6V (*1)
4: 9W (*2)
0: 230V, 1~ (*1)
1: 230V, 3~ (*1)
2: 400V, 3~ (*2)
1: 1/1+2 (*1) (*2)
2: 1/2
3: 1/2 + 1/1+2 in emergency
0~10kW, step: 0,2kW
2kW (*1)
3kW (*2)
0~10kW, step: 0,2kW
4kW (*1)
6kW (*2)
0: Allowed
1: Not allowed
-15~35°C, step: 1°C
0°C
0: Disabled
1: Enabled
2: Only DHW
0~10kW, step: 0,2kW
0kW
20~95 min, step: 5 min
50 min
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Legionella only
0: Manual
1: Automatic
0: Disabled
1: Enabled
-15~35°C, step: 1°C
0°C
0~20°C, step: 1°C
10°C
0~10 hour, step: 0,5 hour
0,5 hour
0~20 min, step 1 min
1 min
5~95 min, step: 5 min
30 min
0~95 min, step: 5 min
95 min
0: Intermittent
0: No
1: Active open
2: Active closed
3: Safety thermostat
0: None
1: BSH only
2: BUH only
3: All heaters
0: Forced off
1: As normal
0: No limitation
1: Continuous
2: Digital inputs
0: Current
1: Power
0~50 A, step: 1 A
50 A
0~50 A, step: 1 A
50 A
5/10
Installer setting at variance with
default value
Date
Value
4P556077-1 - 2018.12

Advertisement

Table of Contents
loading

Table of Contents