3. ELECTRONIC EQUIPMENT JE275
!
Before performing any work on the electronic equipment (connections, maintenance), always turn the power off.
Install a differential thermal breaker upstream with adequate tripping threshold (0.03A).
Connect the ground cable to the terminal on the J9 connector on the equipment (14).
Check that the mains switch is equipped with a locking key, unless this is fitted under the supervision of the operator/maintainer
The equipment must be installed at a height between 0.4 m and 2.0 m.
3.1 ELECTRICAL CONNECTIONS
JE275 BOARD SIDE
J9
MOT2
COM
MOT1
FAN
COM
COM
LAMP
J2
GND
OUT 4
OUT 3
OUT 3
OUT 2
OUT 1
+24 V
+24 V
GND
GND
EMERGENCY
STOP
FSW
CLOSE
OPEN A
LOOP 2
LOOP 2
LOOP 1
LOOP 1
J1
EFO N.O. connection (activtes also in case of black out)
GND
EMERGENCY
4
5
Bollard side
www.FastGateOpeners.com | (800) 878-7829 | Sales@FastGateOpeners.com
L N
A1
1
3
2
4
J3
J5
Limit switch
UP
Limit switch
DOWN
R1
R1
230 V~
Board side
BOLLARD SIDE
A1
5
13
A1
Contactor
6
14
A2
CL
Solenoid valve
EFO
solenoid valve
Heater
(optional)
EFO pressure
switch
EFO N.C. connection (voluntary activation only)
GND
EMERGENCY
4
5
Bollard side
FG7OR - 3G4
FG7OR - 16G1,5
Motor
COM
AP
PE
1
2
3
4
Refer to the
diagram below
5
6
230 V ~
7
230 V ~
8
+24V
+24V
9
Lights
10
Limit switch UP
11
Limit switch DOWN
Limit switch common
12
R1
R1
230 V~
Board side
14