Honeywell FIRE-LITE MS-10UD Series Manual page 120

Fire alarm control panels
Hide thumbs Also See for FIRE-LITE MS-10UD Series:
Table of Contents

Advertisement

NFPA Standard-Specific Requirements
Notes:
1.
Reference the 411UD Manual for additional information
2.
Program the 411UD for slave operation
3.
The MS-5UD/MS-10UD must be programmed for AC Loss Reporting Delay This prevents the immediate transmission of a trouble
on the loss of AC power
4.
All connections between the control panel and the 411UD must be in conduit, less than 20 feet (610 cm) in length, in the same room
5.
Any zone of the 411UD can be wired to function as alarm, trouble or supervisory. In Figure B.1 on page 119, Channel 1/Zone 1 is
wired to the control panel's alarm relay, Channel 2/Zone 2 is wired to the control panel's trouble relay and Channel 3/Zone 3 is
wired to the control panel's supervisory relay
6.
Nonresettable 24 VDC power is supplied to the 411UD via TB9 terminals configured for nonresettable power on the FACP. Jumper
J4 on the 411UD must be removed for 24 VDC power
7.
End-of-Line resistors must terminate all 411UD circuits, including unused circuits
8.
A -VDC from the 411UD Trouble Contacts will activate the Trouble Input J6 on the FACP
NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate transmission of sprinkler supervisory or
trouble conditions.
Notes:
1.
3 ohms maximum loop resistance allowed for wiring from
control panel to Municipal Box.
2.
Cut JP30 on the MS-5UD/MS-10UD main circuit board to
supervise placement of 4XTMF module and circuit.
3.
Cut JP24 on the MS-5UD/MS-10UD main circuit board to
enable FACP Supervisory relay.
4.
Refer to "4XTMF Transmitter Module Installation" on
page 33 for detailed information.
120
Polarities shown in alarm condition
Figure B.2 Municipal Box Connected to 4XTMF Transmitter Module
Municipal Box Circuit
Nonpower-limited
-
+
4XTMF
MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018
FIRE
+
-
Gamewell Model M34-56
Local Energy Municipal
Box

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents