(B) Outdoor Unit - Technibel SPA250R5TAA Technical & Service Manual

Table of Contents

Advertisement

1. SPECIFICATIONS
1-2 Major Component Specifications
(B)
Outdoor Unit
Unit Model No.
Source
Controller P.C.B. Ass'y
Control circuit fuse
Compressor
Model...number
Source
Nominal output
Compressor oil
Coil resistance
(Ambient temperature 25 °C)
Safety devices
Overload relay models
Operating temperature
Crank case heater
Refrigerant amount at shipment
High pressure switch
Set pressure
Fan
Number...diameter
Fan speeds
Fan motor
Model
Source
No. of pole...rpm (230 V, High)
Nominal output
Coil resistance
(Ambient temperature 20 °C)
Safety device
Operating temperature
Run capacitor
Heat exchange
Coil
Rows...fin pitch
Face area
W
cc
Open °C
Close °C
kg
OFF kg/cm
2
2
ON
kg/cm
mm
W
WHT – BRN :127.3
WHT – VLT : 56.7
Open °C
Close °C
VAC, µF
mm
2
m
– 11 –
GR250R5TAA
220 - 240 V / 1 phase / 50 Hz
CR-C253GH5 (Microprocessor)
250 V, 3.15 A
Rotary (Hermetic)
C-R221H5W
220 - 240 V / 1 phase / 50 Hz
2200
1500
C - R : 0.76
,
R - S : 3.52
C - S : 2.76
Internal type
160 ± 5
87 ± 11
240 V 25 W
R-22 - 3.0
ACB - 1TB07
+2.0
30
+0.5
24 ± 2.0
Propeller
1...ø460
2 (AUTO)
KFC6T-91C5P
220 - 230 - 240 V / 1 phase / 50 Hz
6...772
70
,
VLT – YEL : 15.0
,
YEL – PNK :
Internal type
130 ± 8
79 ± 15
440 V, 6 µF
Aluminium plate fin, Copper tube
2...2.0
0.616
7.2

Advertisement