(B) Outdoor Unit - Technibel SPA250X5TAA Technical & Service Manual

Table of Contents

Advertisement

1. SPECIFICATIONS
1-2 Major Component Specifications

(B) Outdoor Unit

MODEL No.
Source
Compressor
Model ... Code No.
Nominal output
Compressor oil
Coil resistance (at 25°C)
Refrigerant amount at shipment
Safety device
Operating temperature
Run capacitor
High pressure switch
Set pressure
Fan (Number...diameter (mm))
Fan motor
Model...Nominal output
No. of pole ... rpm (230V, High)
Coil resistance
(Ambient temperature 20°C)
Safety device
Operating temperature
Run capacitor
Heat exchanger
Coil
Rows ... fin pitch
Face area
W
cc
kg
°C
Open
°C
Close
V, µF
2
OFF kg/cm
2
ON
kg/cm
W
rpm
°C
Open
°C
Close
VAC, µF
mm
m
2
– 10 –
GR250X5TAA
220 - 230 - 240 V / 1 phase / 50 Hz
Rotary (Hermetic)
C - R221H5V
2,200
1,350
C - R : 0.76, C - S :2.76
R22 - 2.4
Internal / OL - D24
160 ± 5 / 150 ± 10
87 ± 9 / 63 ± 10
400V, 40
ACB - 1TB07
+ 2.0
30
+ 0.5
24 ± 2.0
Propeller (1...ø 460)
KFC6S - 91C5P...100 W
6...868
BRN – WHT
:
61.0
YEL – PNK
:
17.7
WHT – YEL
:
64.3
Internal type
130 ± 8
79 ± 15
440 V, 5 µF
Aluminium plate fin / Copper tube
2...2.0
0.616

Advertisement

Table of Contents
loading

Table of Contents