Technibel SPA250R5TAA Technical & Service Manual page 12

Table of Contents

Advertisement

1. SPECIFICATIONS
(B)
Outdoor Unit
Unit Model No.
Source
Controller P.C.B. Ass'y
Control circuit fuse
Compressor
Model...number
Source
Nominal output
Compressor oil
Coil resistance
(Ambient temperature 25 °C)
Safety devices
Overload relay models
Operating temperature
Crank case heater
Refrigerant amount at shipment
High pressure switch
Set pressure
Fan
Number...diameter
Fan speeds
Fan motor
Model
Source
No. of pole...rpm (230 V, High)
Nominal output
Coil resistance
(Ambient temperature 20 °C)
Safety device
Operating temperature
Run capacitor
Heat exchange
Coil
Rows...fin pitch
Face area
W
cc
°C
Open
°C
Close
kg
OFF kg/cm
2
2
ON
kg/cm
mm
W
WHT – BRN :127.3
WHT – VLT : 56.7
°C
Open
°C
Close
VAC, µF
mm
2
m
– 12 –
GR250R7TAA
380 - 400 - 415 V / 3 phase / 50 Hz
CR-C253GH (Microprocessor)
250 V, 3.15 A
Rotary (Hermetic)
C-R224H8U
380 - 400 - 415 V / 3 phase / 50 Hz
2400
1350
T - R : 5.54
,
R - S : 5.54
S - T : 5.54
Internal type
120 ± 5
98 ± 11
240 V 25 W
R-22 - 3.0
ACB - 1TB07
+2.0
30
+0.5
24 ± 2.0
Propeller
1...ø460
2 (AUTO)
KFC6T-91C5P
220 - 230 - 240 V / 1 phase / 50 Hz
6...772
70
,
VLT – YEL : 15.0
,
YEL – PNK :
Internal type
130 ± 8
79 ± 15
440 V, 6 µF
Aluminium plate fin / Copper tube
2...2.0
0.616
7.2

Advertisement