4. SERVICE PROCEDURES
2) Symptom: LCD on the remote controller displays "CHECK E01". (Unusual
communication between remote controller and indoor unit.)
Start
Remote controller judges itself
with self-diagnostic functions
OK
Is there an open or a contact
defect in the No. 1 line of the
remote controller?
No
Is there 200 -240 V AC between
U1 and U2 of 8 P terminal plate?
No
Is the indoor unit PCB's non-volatile
memory IC ("CHECK F29"
displayed) wrong?
No
Is the indoor unit PCB's FORCED
OPR pin shorted?
No
Replace the indoor unit PCB.
3) Symptom: LCD on the remote controller displays "CHECK E02". (Unusual
communication between remote controller and indoor unit)
Is the No. 1 line wire (red) for the
remote controller connected to
another line (2 or 3) or are No. 1
and No. 3 (black) wired reversed?
Remote controller judges itself with
self-diagnostic functions.
(To avoid misjudgment, always
remove the No. 1 line of the remote
controller wiring from the indoor
unit terminal plate.)
Replace the indoor unit PCB.
NG
Replace the remote controller.
Yes
Correct the wiring.
Mis-wiring between the power
Yes
supply line and indoor/ outdoor
unit operation lines.
Yes
Replace the memory IC
Yes
Open the FORCED OPR pin.
Start
Yes
No
NG
OK
Yes
Repair the wiring.
Replace the remote controller.
72
Correct the wiring, and pull out the
socket connected to the OC plug
to replace with the EMG plug.