Encoder cable: For best shielding use cable with an overall shield and individual shields on twisted
pairs, connect the cable as illustrated in Figure 3-4. Clamp the overall shield to grounded metallic
surfaces at both the encoder and the drive.
Brake resistor cable: The optional braking resistor should also be wired with shielded cable. If
unshielded wire is required refer to the Drive User Guide for guidance.
Control cables: If the control wiring is to leave the enclosure, it must be shielded and the shield(s)
clamped to the drive using the grounding bracket. Remove the outer insulating cover of the cable to
ensure the shield(s) make contact with the bracket, but keep the shield(s) intact until as close as
possible to the terminals.
Figure 3-4 Feedback cable shield connections
Shield
connection
to 0V
Connection
at drive
3.4

Control connections

For information on control connections, refer to the back cover of this guide.
Unidrive M702 / HS72 Control Getting Started Guide
Issue Number: 2
Twisted
pair
shield
Cable
Cable
Ground clamp
shield
on shield
Twisted
pair
Shield
shield
connection
to 0V
Connection
at motor
Cable
shield