6.2.2
RFC-A mode (with position feedback)
Induction motor with position feedback
For simplicity only an incremental quadrature encoder will be considered here. For information on
setting up one of the other supported speed feedback devices, refer to Setting up a feedback device
in the Drive User Guide.
Action
Ensure:
Before
Drive Enable signal is not given (terminal 11 and 13)
power-up
Run signal is not given
Motor and feedback device are connected
Verify that RFC-A mode is displayed as the drive powers up. If the
mode is incorrect see section section 4.7
Power-up
mode
the drive
Ensure:
Drive displays 'Inhibit'
Incremental encoder basic set-up
Enter:
Drive encoder type in Pr 03.038 = AB (0): Quadrature encoder
Encoder power supply in Pr. 03.036 = 5 V (0), 8 V (1) or 15 V (2).
NOTE
Set motor
feedback
parameters
CAUTION
Drive encoder Lines Per Revolution (LPR) in Pr 03.034 (set
according to encoder)
Drive encoder termination resistor setting in Pr 03.039:
Enter:
Motor rated frequency in Pr 00.047 (Hz)
Enter motor
Motor rated current in Pr 00.046 (A)
nameplate
Motor rated speed in Pr 00.045 (rpm)
details
Motor rated voltage in Pr 00.044 (V) - check if
Set
Enter:
maximum
Maximum speed in Pr 00.002 (rpm)
speed
Enter:
Set
Acceleration rate in Pr 00.003 (s/1000 rpm)
acceleration
Deceleration rate in Pr 00.004 (s/1000 rpm) (If braking resistor
/
installed, set Pr 00.015 = FAST. Also ensure Pr 10.030, Pr 10.031
deceleration
and Pr 10.061 are set correctly, otherwise premature 'Brake R Too
rates
Hot' trips may be seen).
36
on page 19.
If output voltage from the encoder is >5 V, then the
termination resistors must be disabled Pr 03.039 to 0.
Setting the encoder voltage supply too high for the encoder
could result in damage to the feedback device.
0 = A-A\, B-B\, Z-Z\ termination resistors disabled
1 = A-A\, B-B\, termination resistors enabled, Z-Z\ termination
resistors disabled
2 = A-A\, B-B\, Z-Z\ termination resistors enabled
Detail
Changing the operating
or
Unidrive M702 / HS72 Control Getting Started Guide
Mot X XXXXXXXXX
No XXXXXXXXXX kg
IP55
I.cl F
°
C 40 s S1
V
Hz min
230
50 1445 2.20 0.80 8.50
400
CN = 14.5Nm
connection
240
50 1445 2.20 0.76 8.50
415
CN = 14.4Nm
CTP- VEN 1PHASE 1=0,46A P=110W R.F 32MN
0.02
1000rpm
0.03
Issue Number: 2
-1
kW
cosφ
A
4.90
4.90
t
t
0.04