9

Technical data

Table 11: Technical data, dimensions and weights.
Technical data
Dimensions (W x H x D)
Weight
Table 12: Technical data, general data.
Technical data
Power supply
Dielectric strength
Connection type
Max. output
Max. power consumption 3.5 W
UPS
Charge
Display
Diagnostic LED
Approvals
Table 13: Technical data, I/O terminals.
Technical data
I/O connection
Power supply for I/O
terminals
Power contacts current
loading
Process data on the K-
bus
max. number of terminals
(K-bus)
max. number of terminals
(E-bus)
Table 14: Technical data, environmental conditions.
Technical data
Ambient temperature
during operation
Ambient temperature
during storage
Relative humidity
Shock resistance
Vibration resistance
EMC immunity
EMC emission
Protection class
CX2100-0004
CX2100-0004
40 mm x 100 mm x 91 mm
375 g
CX2100-0004
24 V DC (-15 %/+20 %)
500 V (supply / internal electronics)
spring-loaded system
45 W
-
-
FSTN display 2 lines x 16 characters of text, illuminated
1 x PWR, 1 x I/O Run, 1 x I/O Err
CE, UL
CX2100-0004
K-bus or E-bus, automatic recognition
max. 2 A
max. 10 A
max. 2048 bytes input and 2048 bytes output
64 (255 with K-bus extension)
Up to 65534 terminals
CX2100-0004
-25° C ... +60° C
-40° C ... +85° C
95% no condensation
conforms to EN 60068-2-27
conforms to EN 60068-2-6
conforms to EN 61000-6-2
conforms to EN 61000-6-4
IP 20
Version: 1.2
Technical data
47