Step 13 Optional: Extending The Power Cable - Samsung AC BN6DCH Series Installation Manual

Hide thumbs Also See for AC BN6DCH Series:
Table of Contents

Advertisement

• Screws on terminal block must not be unscrewed with
the torque less than 0.89 lbf.ft.
• Since it has the external power supply, refer to the
outdoor unit installation manual for MAIN POWER.
• When installing the indoor unit in a computer room,
use the double shielded (tape aluminum / polyester
braid + copper) cable of FROHH2R type.
Step 13 Optional: Extending the
power cable
1 Prepare the following tools.
Tools
Spec
Crimping pliers
MH-14
Connection sleeve
0.79xØ0.26 (20xØ6.5)
(inch (mm))
(HxOD)
Insulation tape
Width 0.75 inch (19 mm)
Contraction tube
2.76xØ0.31 (70xØ8.0)
(inch (mm))
(LxOD)
2 As shown in the figure, peel off the shields from the
rubber and wire of the power cable.
• Peel off 0.79 inch (20 mm) of cable shields from the
pre-installed tube.
CAUTION
• For information about the power cable specifications
for indoor and outdoor units, refer to the installation
manual.
• After peeling off cable wires from the pre-installed
tube, insert a contraction tube.
• If cable wires are connected without using connecting
sleeves, their contact area becomes reduced, or
corrosion develops on the outer surfaces of the wires
(copper wires) over a long time. This may cause an
increase of resistance (reduction of passing current)
and consequently may result in a fire.
Power cable
2.36 (60)
0.79 (20)
3 Insert both sides of core wire of the power cable into
the connection sleeve.
• Method 1: Push the core wire into the sleeve from
both sides.
• Method 2: Twist the wire cores together and push it
into the sleeve.
Shape
Method 1
Connection sleeve
4 Using a crimping tool, compress the two points and
flip it over and compress another two points in the
same location.
• The compression dimension should be 8.0.
• After compressing it, pull both sides of the wire to
make sure it is firmly pressed.
Method 1
Compress it 4 times.
0.20 inch (5 mm)
0.79
0.79
(20)
(20)
2.36 (60)
4.72 (120)
7.09 (180)
7.09 (180)
4.72 (120)
0.79 (20)
0.79 (20)
Method 2
Connection sleeve
Compression
dimension
Method 2
Compress it 4 times.
0.20 inch (5 mm)
Unit : inch (mm)
0.79 (20)
Pre-installed tube
for the power
cable
21