Installation Procedure
Model
Net dimension (W x D x H)
Liquid pipe connection
Gas Pipe connection
Drain hose connection
• The circular panel is by default available in exposed
installation.
• Make inspection holes on the ceiling for easier
installation and maintenance, as shown in the
following table. (The size of an inspection hole must be
at least 17.72 x 17.72 inch (450 X 450 mm)
• A suspended ceiling structure can substitute for the
inspection holes.
Category
Recessed installation
Integrated
Square panel
1 ea
Circular panel
2 ea
Spacing requirements
A
A
A: 59.10 inch (1500mm) or more
Model
AC018BN6DCH
inch
C
10.27 (261)
(mm)
8
English
AC018BN6DCH
37.28 x 37.28 x 11.06
inch (mm)
(947 x 947 x 281)
inch (mm)
1/4 (6.35)
inch (mm)
1/2 (12.7)
inch (mm)
Inspection hole
Exposed
installation
suspended
-
A
A
AC024BN6DCH
AC030BN6DCH
13.58 (345)
13.58 (345)
AC024BN6DCH
AC030BN6DCH
37.28 x 37.28 x 14.37
(947 x 947 x 365)
1/4 (6.35)
5/8 (15.88)
Outer diameter: 1.26 (32.0), inner diameter: 1.04 (26.5)
• For the recessed installation of the circular panel
Inspection hole
Indoor unit
display
Connection part of the
drain hose
NOTE
• The clearance between the panel and the inspection
hole is 0.59 to 0.79 inch (15 to 20 mm) on a side.
'C'
AC036BN6DCH
13.58 (345)
AC036BN6DCH
AC042BN6DCH
AC048BN6DCH
3/8 (9.52)
3/8 (9.52)
5/8 (15.88)
5/8 (15.88)
Unit: inch (mm)
41.37 (1050)
34.79 (883)
Refrigerant
pipe
ø39.76 to 40.16
Inspection hole
(ø1010 to 1020)
Ceiling opening diameter
ø39.76 to 40.16
(ø1010 to 1020)
Unit: inch (mm)
Indoor unit
0.39 (10)
0.79 (20)
98.5 (2500) or more
59.10 (1500)
or more
Obstruction
AC042BN6DCH
AC048BN6DCH
13.58 (345)
13.58 (345)