Step 5 Optional: Extending The Power Cable - Samsung AC BXADCH Series Installation Manual

Hide thumbs Also See for AC BXADCH Series:
Table of Contents

Advertisement

Outdoor-to-indoor power and communication
cables specifications
• Indoor unit :
1WAY CST(AC***BN1***)
360CST(AC***BN6***)
4WAY CST(AC***BN4***)
Mini4way CST(AC***BNN***)
Console(AC***BNJ***)
RAC(AC***BNT***, AC***BNA***)
Indoor power supply
Power supply
1Φ, 208-230V~, 60Hz
Communication cable
0.0012 inch²↑ (0.75mm2 ↑), 2 wires
• Indoor unit :
Duct(AC***BNL***, AC***BNH***)
Indoor power supply
Power supply
1Φ, 208-230V~, 60Hz
Communication cable
0.0012 inch²↑ (0.75mm2 ↑), 2 wires
• Indoor unit :
MPAH(AC***BNZ***)
Indoor power supply
Power supply
1Φ, 208-230V~, 60Hz
Communication cable
0.0012 inch²↑ (0.75mm2 ↑), 2 wires
• Power supply cords of parts of appliances for outdoor
use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 57 /
CENELEC: H05RN-F)
• When installing the indoor unit in a computer room or
network room, use the double shielded (tape aluminum /
polyester braid + copper ) cable of FROHH2R type.
DB68-11274A-00_IM_CAC Universal Outdoor_AA_EN.indd 17
DB68-11274A-00_IM_CAC Universal Outdoor_AA_EN.indd 17
Max/Min (V)
Indoor power cable
0.0012 inch²↑
±10%
(0.75mm2 ↑), 3 wires
Max/Min (V)
Indoor power cable
0.0023 inch2 ↑
±10%
(1.5mm2 ↑), 3 wires
Max/Min (V)
Indoor power cable
0.0039 inch2 ↑
±10%
(2.5mm2 ↑), 3 wires
Step 5 Optional: Extending the
power cable
1 Prepare the following tools.
Tools
Spec
Crimping pliers
MH-14
Connection sleeve
0.78 (20)x
[Inch(mm)]
Ø0.25 (6.5) (HxOD)
Insulation tape
Width 19 mm
Contraction tube
2.75 (70)x
[Inch(mm)]
Ø0.31 (8.0) (LxOD)
2 As shown in the figure, peel off the shields from the
rubber and wire of the power cable.
• Peel off 0.79 inch (20 mm) of cable shields from the
pre-installed tube.
Power cable
0.79
(20)
7.09
(180)
7.09
(180)
4.72
(120)
2.36
(60)
0.79
0.79
(20)
(20)
CAUTION
• For information about the power cable specifications
for indoor and outdoor units, refer to the installation
manual.
• After peeling off cable wires from the pre-installed
tube, insert a contraction tube.
Shape
[Unit : inch(mm)]
0.79
0.79
(20)
(20)
2.36
(60)
4.72
(120)
Pre-installed
0.79
tube for the
(20)
power cable
17
English
2021-09-14 오전 9:21:58
2021-09-14 오전 9:21:58