Step 13 Optional: Extending The Power Cable - Samsung ACBN1DCH Series Installation Manual

Table of Contents

Advertisement

Indoor power supply
Power supply
Max/Min(V)
208 to 230V, 60 Hz
Communication cable
0.0012 inch² ↑(0.75mm²↑), 2 wires
AC power: M4 screw
0.43(11)
0.51(13)
M3.5
M4
(1N‧m=10kgf‧cm)
• Power supply cords of parts of appliances for outdoor use shall
not be lighter than polychloroprene sheathed flexible cord.
– Code designation
[1-phase] IEC: 60245 IEC 57 / CENELEC: H05RN-F grade
or more
• Since it has the external power supply, refer to the
outdoor unit installation manual for MAIN POWER.
CAUTION
• When installing the indoor unit in a computer
room or network room, use the double shielded
communication cable (tape aluminum / polyester
braid + copper) of FROHH2R type.
DB68-11272A-00_IM_CAC WindFree1,4way_AA_EN_.indd 23
DB68-11272A-00_IM_CAC WindFree1,4way_AA_EN_.indd 23
Indoor power cable
0.0012 inch² ↑
±10%
(0.75mm²↑), 3 wires
Unit: inch(mm)
Communication: M3.5 screw
0.3(7.5)
0.35(9)
Tightening torque
N‧m
lbf.ft
0.8 to 1.2
0.59 to 0.89
1.2 to 1.8
0.89 to 1.1

Step 13 Optional: Extending the power cable

1 Prepare the following tools.
Tools
Spec
Crimping pliers
MH-14
Connection sleeve
20xØ6.5
(mm)
(HxOD)
Width 19
Insulation tape
mm
Contraction tube
70xØ8.0
(mm)
(LxOD)
2 As shown in the figure, peel off the shields from the
rubber and wire of the power cable.
• Peel off 20 mm of cable shields from the pre-
installed tube.
CAUTION
• For information about the power cable
specifications for indoor and outdoor units, refer to
the installation manual.
• After peeling off cable wires from the pre-installed
tube, insert a contraction tube.
• If cable wires are connected without using
connecting sleeves, their contact area becomes
reduced, or corrosion develops on the outer
surfaces of the wires (copper wires) over a long
time. This may cause an increase of resistance
(reduction of passing current) and consequently
may result in a fire.
Power cable
20
180
180
120
60
20
20
Shape
(Unit: mm)
20
20
60
120
Pre-installed
tube for the
20
power cable
23