Levelflex FMP56, FMP57
Factory setting
Display interval
Navigation
Description
Input range
Facotry setting
Distance unit
Navigation
Description
Selection
Factory setting
Bin property
Navigation
Description
Selection
Endress+Hauser
30 %
Display/operation ® Display interval
Setup ® Advanced Setup ® Display ® Display interval
Use this function to set the length of time the measured values are displayed if the values alternate
on the display. This type of alternating display only occurs automatically if the number of measured
values defined exceeds the number of values the selected display format can display simultaneously.
• The Value 1 display - Value 4 display parameters are used to specify what measured
values are shown on the display (® ä 117).
• The display format of the displayed measured values is specified using the Format display
parameter (® ä 88).
1 to 10 s
5 s
18.2
"Setup" menu
Setup ® Distance unit
Defines the distance unit
• m
• ft
• in
• mm
m
Setup ® Bin property
Defines the bin property
• Concrete
• Plastics / wood
• Metallic
• Aluminium
Description of device parameters
91