Fire-Lite Alarms UDACT-F Installation, Operation, And Programming Manual page 41

Universal digital alarm communicator/transmitter
Table of Contents

Advertisement

Technical Manuals Online! - http://www.tech-man.com
To access Type Mode, press the MODE key followed by the 4-digit code 8973 and
then press the [ENTER/STORE] key. The UDACT-F will display three digits. For
example, initial entry will display 01 0.
The characters to the left identify the zone or point number. In this example, 01
identifies zone 01 or point address 01. The character to the right (0 in this example)
identifies the type of zone or point as follows:
0 = Zone or point defined as fire alarm
1 = Disable zone or point report
2 = Zone or point defined as supervisory
3 = Zone or point defined as pullstation
4 = Zone or point defined as heat detector
5 = Zone or point defined as waterflow
6 = Zone or point defined as duct detector
7 = Zone or point defined as flame sensor
8 = Zone or point defined as smoke zone (Use for M302 modules
monitoring conventional smoke detectors. In point reporting,
addressable detectors automatically report as detectors eliminating the
need for Type Mode entry).
Factory default is all zones or points set to 0 for fire alarm. Zone reporting allows
the mixing of types of devices on a single zone. To change the type definition of the
zone or point from the factory default, select 2 to 8 corresponding to the type of
device(s) used (do not mix device types for these settings), or select 1 to disable
alarm reporting of any zone or point. The digit entered will appear on the far right
display. Next press the [ENTER/STORE] key. This stores the entry into E
and increments to the next higher address.
Use the UP, DOWN and 1st EVENT keys to move through the list of 56 zones or
198 points (refer to Appendices D & E), similar to the method described in the
programming section of this manual. For MS-9200 applications, when address 56 is
programmed as a 3 or 4 for point reporting, detectors are reported as points 001 to
099 and modules are reported as points 101 to 199. When address 56 is programmed
as a 5 or 6 for code wheel matching point reporting, detectors and modules report as
001 - 099 (the actual device address).
To define all zones or points as fire alarm (return to original factory default settings)
enter zone or point 999 and then press the [ENTER/STORE] key. The display will
change to 01 0, indicating a return to the factory default settings.
4.2.1 Disabling of Zones or Points
This feature is primarily used when system points have been defined as remote reset,
acknowledge, silence or drill switches. Refer to the FACP technical manual for
additional information. Activation of remote switches appear as alarms on the EIA-
485 bus while in point type of annunciation. The UDACT-F will report these points
as fire alarm points unless disabled in the Type Mode. Disabling zones or points
also prohibits the activation (shorted or alarm activated condition) from being
reported by the UDACT-F. Disabling of the zone or point does not affect the
reporting of the zone or point trouble condition.
4.2.2 Zone or Point Supervisory
A zone or point must be defined as supervisory to allow the UDACT-F to identify
the correct report to transmit to the central station. Follow the programming
instructions in the FACP manual to program a zone or point as supervisory. Next
program the zone or point as a code 2 for supervisory. Use the charts in Appendices
D, E and F to enter point and zone definitions. Note that the UDACT-F fire
protection and reporting capabilities are inactive while in Type Mode.
Document # 50049 Rev D 5/2/97 P/N 50049:D
firealarmresources.com
2
memory
41

Advertisement

Table of Contents
loading

Table of Contents