Fire-Lite Alarms UDACT-F Installation, Operation, And Programming Manual page 33

Universal digital alarm communicator/transmitter
Table of Contents

Advertisement

Technical Manuals Online! - http://www.tech-man.com
3+1, 4+1 Express or 4+1 Standard Formats
If '0, 2, 4, 6 or 8' are entered for address 42, the following is automatically programmed
for the Secondary phone number event codes. Enter a '0' for the data setting to disable the
report.
Address
Description
139
Secondary # General Alarm Code
140
Secondary # Zone/Point Alarm Code
141
Secondary # General Supervisory Code
142
Secondary # Zone/Point Supervisory Code
143
Secondary # General Fault Code
144
Secondary # AC Fault Code
145
Secondary # Zone/Point Fault Code
146
Secondary # Low Battery Fault Code
147
Secondary # Telco Primary Line Fault Code
148
Secondary # Telco Secondary Line Fault Code
149
Secondary # NAC Fault Code
150
Secondary # Comm. Trouble Primary # Code
151
Secondary # Comm. Trouble Secondary # Code
152
Secondary # 485 Comm. Trouble Code
153
Secondary # System Off Normal Code
154
Secondary # UDACT-F Off Normal Code
155
Secondary # General Alarm Restore Code
156
Secondary # Zone/Point Alarm Restore Code
157
Secondary # General Supervisory Restore Code
158
Secondary # Zone/Point Supervisory Restore Code
159
Secondary # General Fault Restore Code
160
Secondary # AC Fault Restore Code
161
Secondary # Zone/ Point Fault Restore Code
162
Secondary # Low Battery Fault Restore Code
163
Secondary # Telco Primary Line Fault Restore Code
164
Secondary # Telco Secondary Line Fault Restore Code
165
Secondary # NAC Fault Restore Code
166
Secondary # Comm.Trouble Primary # Restore Code
167
Secondary # Comm. Trouble Secondary # Restore Code
168
Secondary # 485 Comm. Trouble Restore Code
169
Secondary # System Off Normal Restore Code
170
Secondary # UDACT-F Off Normal Restore Code
171
Secondary # System 24 Hour Test
172
Secondary # System 24 Hour Test w/active event
173
Secondary # Manual Test
Note: Zero entries prevent the transmission of the report to the Central Station.
Table 3-5: Event Codes, Secondary Number
Document # 50049 Rev D 5/2/97 P/N 50049:D
firealarmresources.com
Setting
1
0
8
0
F
F
0
F
F
F
F
F
F
F
F
F
E
0
E
0
E
E
0
E
E
E
E
E
E
E
E
E
9
F
9