Sensiscan 2000 - Fire-Lite Alarms UDACT-F Installation, Operation, And Programming Manual

Universal digital alarm communicator/transmitter
Table of Contents

Advertisement

CPU-2000
16
Technical Manuals Online! - http://www.tech-man.com

2.2.2 Sensiscan 2000

Remove all power from the control panel by disconnecting AC and batteries. Install
the three supplied nylon support posts for the top and bottom left of the UDACT-F,
one aluminum/nylon and one aluminum standoff in the CHS-4 chassis slot in which the
UDACT-F is to be installed (refer to Figure 2-4). Position the UDACT-F on the standoffs
and secure on aluminum standoff with a #6-32 screw. Alternatively, the UDACT-F
may be mounted remotely using an ABS-8RF or UBS-1F enclosure. Ferrite cores are
recommended for this application. Refer to Figure 2-3 and the accompanying Notes
for wiring alternatives.
Connect the communication line between the EIA-485 terminal block on the CPU-2000
and TB-1 terminals 3 and 4 on the UDACT-F being certain to observe polarity (refer to
Figure 2-5). Recommended wire is 12 AWG to 18 AWG twisted pair. If no other devices
are connected to the EIA-485, install a 120 ohm EOL resistor across UDACT-F TB1
terminals 3 and 4.
Connect the supplied Ground Strap from the UDACT-F Earth Ground terminal on TB3
to the CHS-4 chassis. Connect 24VDC filtered, regulated, non-resettable power to TB-
1 terminals 1 and 2 on the UDACT-F (refer to Figure 2-6).
CHS-4
Aluminum Standoff
and screw
Figure 2-4: UDACT-F Mounting in CHS-4
Document # 50049 Rev D 5/2/97 P/N 50049:D
firealarmresources.com
UDACT-F
Nylon
Support
Posts
Ground
Strap
Nylon &
Aluminum
Standoff