Installation and disassembly

4.2 Types of installation

Further notes
NOTICE
Warming and premature aging of the network component due to direct sunlight
Direct sunlight can heat up the device and can lead to premature aging of the network
component and its cabling.
Provide suitable shade to protect the network component against direct sunlight.
4.2
Types of installation
Types of installation
For the device, you have the following options:
• Wall mounting (no ceiling mounting)
• Installation on a DIN rail
• Installing on the S7-300 standard rail
• Installing on the S7-1500 standard rail
• Installation in a 19" mounting frame
• Installation on a desktop pedestal
Strain relief for the cables
Regardless of the type of installation, make sure that there is suitable strain relief for the
connecting cable.
Shielding of cables
If cables are installed permanently, it is advisable to remove the insulation of the shielded cable
and to establish contact on the shield/PE conductor bar.
Installation clearance
Keep to the minimum clearances to other components or to walls of a housing so that the
convection ventilation of the device is not blocked.
• Below at least 10 cm
• Above at least 10 cm
20
Operating Instructions, 06/2022, C79000-G8976-C447-03