Intelligent Test Switch Module with Dual Isolators
INTRODUCTION
The Model TSM-1X Intelligent Test Switch Module, P/N
S54370-B7-A1, from Siemens Industry, Inc. is an
addressable, key-activated momentary switch (T-45)
with a tri-color LED indicator for use with intelligent
duct detectors or other compatible intelligent devices on
the Device Loop Circuit of Siemens Desigo and
Cerberus PRO Fire Alarm Systems (refer to Figure 1).
The key activation will cause its associated intelligent
duct detectors or other smoke detectors and
compatible devices to go into alarm. This alarm
condition will cause all logic associated with the duct
detector to activate. The 3-color LED of the module will
show the status of its associated intelligent duct
detector. The TSM-1X is mounted on a switch plate
and can be installed in a 3½ inch deep single gang box.
The TSM-1X module supports two operation modes:
polarity insensitive mode and isolator mode. The
module can be wired for either mode (refer to Figures
3 to 4). During the isolator mode, the built-in dual
isolators will work at both sides of the module to
isolate the line short in front or behind the module.
Observe precautions for handling
Electrostatic Sensitive Devices.
PROGRAMMING
1. Refer to Figure 2 to locate the programming
holes on back of the TSM-1X.
2. To connect the TSM-1X to the DPU
Programmer/Tester, insert the plug from the DPU
cable provided with the Programmer/ Tester into
the programming holes.
3. To prevent potential damage to the DPU, DO
NOT connect a TSM-1X to the DPU until all
conductors of the same polarity are removed from
the device line of the TSM-1X.
4. Follow the steps in the DPU Manual, P/N 315-
033260, to program the TSM-1X to the desired
address. Record the device address on the label
located on the side of the TSM-1X module.
5.
Add a logic function in the system configuration
tool with the intelligent duct detector or other
compatible intelligent devices that will be tested.
The TSM-1X can now be installed and wired to
the system.
A6V101055486_en--_b
Figure 1
TSM-1X Intelligent Test Switch Module
Figure 2
Connecting to the DPU Plug
Siemens Industry, Inc.
Smart Infrastructure
Florham Park, New Jersey
Programming holes
are polarity insensitive -
Plug can be inserted
in any direction.