Installation and disassembly

4.6 Installing on the S7-1500 standard rail

4.6
Installing on the S7-1500 standard rail
Installation
1. Place the first housing guide of the device on the top edge of the standard rail
2. Using a screwdriver, pull down the catch
3. Swing the device down while pulling down the catch
locks in place.
4. Connect the power supply, refer to the section "Power supply (Page 32)".
5. Connect the device to the local network, refer to the section "Properties and functions
(Page 11)".
6. Connect the terminal via as short a cable as possible ≤ 150 mm and a large cross-sectional
area of 1.5 mm² to the functional ground of the system, see section "Grounding (Page 33)
".
Dismantling
1. Disconnect all connected cables.
2. Using a screwdriver, pull down the catch on the rear of the device.
3. Remove the device from the standard rail.
24
on the rear of the device.
. After it is released, the spring catch