Remote operation
7.1 Operating via AMS Device Manager
7.1.4

Master Reset

A master reset is recommended before first configuring a new device. (Block Status must be
Out of Service to perform a Master Reset.)
1. Navigate to Configure/Setup > Resource > Operation > Methods and click to open the
dialog window.
2. In the General field, click on Master Reset and click Next to perform reset to factory
defaults. Click Next to accept default reset to Factory Defaults.
3. Click FINISH then restart AMS to reload settings. Next, scan the device.
7.1.5

Scan Device

Scan Device uploads parameters from the device (synchronizes parameters) to AMS Device
Manager.
1. Open the pull-down menu Actions – Scan Device (upload parameters from the device to
AMS).
2. The next step when adding a new device is to configure and calibrate the device via the
Quick Start Wizard.
7.1.6

Sensor calibration

The LR250 FF does not need to be calibrated, only configured using the Quick Start Wizard
below.
70
Master Reset
SITRANS LR250 with FOUNDATION FIELDBUS