Inverter/ charger

Advertisement

c) Battery Disconnect Function
Battery Under and Over Voltage Setting
Battery Low Disconnect voltage has selectable range: 21.0 - 24.0V (0.2V steps) (Default 21.0V)
The Battery Low Disconnect Voltage must be with a minimum of 1.0V below the Battery Low
Alarm (BLA) Voltage.
Battery Low Alarm Selectable range: 22.0 – 25.0V (0.2V step) (Default 22.0V)
The Battery Low Alarm Voltage must be with a minimum of 1.0V above the Battery Low Disconnect (BLd)
Voltage and must be with a minimum of 1.0V below the Battery Low Recovery (bLr) Voltage.
Battery Under Voltage Recovery Selectable range: 23.0 - 26.0V (0.2V step) (Default 24.0V)
The Battery Low Recovery Voltage must be with a minimum of 1.0V above the Battery Low Alarm
(bLA) Voltage.
Battery Over
Voltage
33.0 V (Not User selectable)
Disconnect
Battery Over
Voltage
32.0 V (Not User selectable)
Recovery
d) Alarm Function
Alarm Setting
Fault and warning audible alarm can be enabled (On -Default) or disabled (Off).
e) Charger Functions