Here a method is explained to set the input/output relations or the output system of PLC for general equipment
control to the table in compliance with the site.

5-1 Screen Configuration of Table Setting

Clicking [Table setting] of the set menu section displays the table setting screen of PLC software for general
equipment control. On this screen, the function and operation items are set to operate PLC software for
general equipment control and write them into ATA card.
Start the table setting from the top in order.
The set data can also be saved in a file other than ATA card. (Refer to Chapter 4 -2- 2.)
5-2 Setting SET.CSV file
Clicking [Setting SET.CVS file] in the setting sub-menu displays the screen to set the connecting number of
G-50A or the like. This screen is to set the connecting number of G-50A.
Notice
On the screen to set SET.CSV file, the connecting number of G-50A can only be set.
(The demand controller if connected and the objective G-50A for demand value transmission can not be set.)
(1) Set the connecting number of G-50A controlled by PLC for general equipment control to a range of 0 ~ 2
sets.
*The default value is set to [0 set]. The case without G-50A connection (0 set) only applies to operating/monitoring the general
equipment at PLC side.
(2) After finishing the setting, click the [OK] button. The set detail is saved to back to the initial screen.
*Clicking the [Cancel] button returns to the initial screen without saving the set detail.
Figure 5-1. Initial screen
11
Table setting
For setting change of table,
display, writing into ATA card.
Setting SET.CSV file
For setting of connecting number
of G-50A (1 ~ 2 sets)
Setting PARA.CSV file
For setting of output
specification of general
equipment at PLC side
Displaying the table set
detail
For displaying of the set detail of
input/output relation table
Setting the table file
(table.bin)
For setting of input/output
relations. Up to 200 sets
maximum.
Setting ATA card drive
For setting/changing the drive of
PC card locating ATA card
Writing into ATA card
For writing various data files into
ATA card