14.8.3 Digital Output Contacts characteristics
Maximum power applicable (VDC and VAC on resistive load)
Fig. 79
Characteristics of the control module contacts without potential
The contacts without potential control module by special relay.
For the characteristics of the contacts, please see the table and curves givenbelow
Rated voltage
(operating range)
Maximum power applicable
Maximum voltage applicable
Maximum current applicable
Rated current
Maximum contact resistence
Maximum capacity
Maximum closed time
Maximum opening time
Isulation between contacts and coil
Resistance with contacts open
Storage temperature
Temperatura di stoccaggio
Mechanical life
Electrical life
Notes
– In the case of indicative loads, the contacts must the protected against over voltage by means of varistors
– For the other characteristics, please refer to the IEC 60694.5.4.4.5.4 (Ed. 2.2), Classe 3 Standards.
AC resistive load
DC resistive load
Current [A]
0 ... 264 V~ 50/60 Hz
0 ... 280 V–
1500 VA (V a.c. on resistive load)
(V d.c. on resistive load - curve A)
400 V~ 50/60 Hz
300 V–
6 A
6 A (250 V~ 50/60 Hz - resistive load)
< 100 mohm (measured at 6 V– / 1 A)
< 1.5 pF
< 5 ms
< 3 ms
4000 Vrms (50 Hz / 1 min)
Min. 10
3
Mohm (measured at 500 V–)
- 40 °C ... + 85 °C
- 40 °C ... + 100 °C
500,000 operation (at 250 V~ 50/60 Hz -
180 operation/min)
50,000 operation (at 6 A / 277 V~ 50/60 Hz -
resistive load - see curves B and C)
????