Note
Note
32
11.3. Servicing
11.3.1. Interruption devices in general
If cleaning is found to be necessary during the inspections, as specified in par. 10.3., use the
following procedure:
• insulate the working area and make it safe by following the safety regulations specified in the
IEC/DIN VDE Standards.
• general cleaning of the surfaces:
– dry and eliminate any light deposits of dirt using a soft dry cloth;
– more resistant deposits of dirt can be removed using a slightly alkaline household cleanser or
Rivolta BWR 210 type detergent.
• cleaning the insulating surfaces and conductive components:
– light dirt: with Rivolta BWR 210 detergent;
– resistant dirt: with cold 716 type detergent.
After cleaning, rinse thoroughly with clean water and dry carefully.
Only use halogen-free detergents and never 1.1.1-trichloroethane, trichloroethylene or carbon
tetrachloride!
11.3.2. Actuator and transmission system
A functional test of the drive must be carried out:
• when the number the number of operating cycles indicated has been exceeded, or
• during maintenance operations.
Before carrying out the functional test, open the circuit-breaker and
• take it to the test position (withdrawable circuit-breaker) or
• insulate and block the working area and make it safe in conformity with the safety rules and
according to the regulations in force (fixed circuit-breakers)
• follow the procedure for discharging the capacitor
• carry out a visual inspection of the state, removing the front panel, e.g. of:
– lubrication of the ball bearings
– the operation counter
– assembly of the sensors
– the position indicator.
Functional test:
• Connect the power supply voltage.
• Carry out several no-load operations. This test particularly applies to circuit-breakers which are
rarely activated under normal conditions.
To check the capacitor, carry out a rapid O-C-O cycle of operations of the circuit-breaker, by
pressing the pushbuttons on the front of the circuit-breaker in rapid succession.
• The LEDs on the inductive sensors are activated as soon as the circuit-breaker has reached the
closing and opening limit positions.
These operations can only be carried out by ABB personnel or suitably qualified and specially trained
personnel.