Waeco AirCon Service 6300G Operating Manual page 31

A/c service unit

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
4.
To check the zero point of the scales for oil and UV additive, open the cover (13) on the left side and take
the containers off the catches:
• Container for fresh oil (10)
• Container for UV additive (11)
• Drained oil receptacle (12)
When the scales are relieved, press ENTER to confirm. The prompt to remove the containers from the scale
5.
will flash. Once you have set the zero point, the selection menu for the scales appears again.
6.
Return the containers to the operating positions: Reattach the containers for oil (10) and (12) and for the UV
additive (11) to the snap locks and close the cover (13).
7.
Press STOP twice to access the standby menu.
14.4
Changing the dryer filter
1.
In the basic menu use the cursor keys
Short selection
Free selection
Other selections
ENTER-OK
2.
Press ENTER to confirm.
3.
Skip the query requesting CAR DATA.
4.
Select Rec/Recycling phase.
5.
Set the Pressure increase Test time to
6.
Press ENTER to confirm.
7.
Deselect Vacuum phase using
8.
Press ENTER to confirm.
9.
Deselect Filling phase using
10. Press ENTER to confirm.
or
to select Free selection.
.
1
.
No
.
No
English
29