2262
CAPACITY COMPENSATION COEFFICIENT
COMPENSATION COEFFICIENT OF PIPE LENGTH
The figures give the compensation coefficient of pipe length owing to installation position (pipe
length, height difference). Pipe length and height difference are the length and the height
difference between the master outdoor unit and indoor unit.
Cooling
z
Outdoor unit
(Upper)
50
40
30
20
10
0
0
10
20
-10
-20
-30
-40
Outdoor unit
(Lower)
Heating
z
Outdoor unit
(Upper)
50
40
30
20
10
0
0
10
-10
-20
-30
-40
Outdoor unit
(Lower)
COMPENSATION COEFFICIENT OF FROSTING / DEFROSTING
(HEATING OPERATION)
To take the effects of accumulated frost and defrosting operation on heating capacity into
consideration, the capacity of outdoor units should be corrected by compensation coefficient
shown in the table below.
Outdoor temperature
(°CDB / °CWB)
Compensation coefficient
30
40
50
60
70
20
30
40
50
60
70
-15 / -16
-9 / -10
0.96
0.94
- (02 - 144) -
80
90
100
110
120
130
80
90
100
110
120
130
-7 / -8
0 / -1
0.92
0.83
Pipe length
L (m)
140
150
Pipe length
L (m)
140
150
2 / 1
5 / 4
7 / 6
0.84
0.90
1.00