6. Capacity compensation rate for pipe length and height
difference
Indoor unit is higher than outdoor unit
Indoor unit
Connection pipe
6-1. Model: AOBH27CMTA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor unit is higher
than outdoor unit *1
Indoor unit is lower than
outdoor unit *2
6-1. Model: AOBH27CMTA
Height difference H
1
*
H
Outdoor unit
5
7.5
30
—
—
20
—
—
10
—
—
7.5
—
0.988
5
0.992
0.992
0
1.000
1.000
-5
1.000
1.000
-7.5
—
1.000
-10
—
—
-20
—
—
30
—
—
- 46 -
Indoor unit is lower than outdoor unit
Outdoor unit
H
Indoor unit
Connection pipe
Pipe length (m)
10
20
30
—
—
0.930
—
0.953
0.947
0.981
0.968
0.963
0.985
0.972
0.966
0.989
0.976
0.970
0.997
0.984
0.978
0.997
0.984
0.978
0.997
0.984
0.978
0.997
0.984
0.978
—
0.984
0.978
—
—
0.978
6. Capacity compensation rate for pipe length and height difference
2
*
40
50
0.926
0.921
0.941
0.936
0.956
0.951
0.960
0.954
0.964
0.958
0.972
0.966
0.972
0.966
0.972
0.966
0.972
0.966
0.972
0.966
0.972
0.966