Capacity Compensation Rate For Pipe Length And Height Difference; Model: Aobh27Cmta - Fujitsu ASBH27CMTA Design & Technical Manual

Wall mounted type air conditioner
Table of Contents

Advertisement

6. Capacity compensation rate for pipe length and height
difference
Indoor unit is higher than outdoor unit
Indoor unit
Connection pipe

6-1. Model: AOBH27CMTA

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor unit is higher
than outdoor unit *1
Indoor unit is lower than
outdoor unit *2
6-1. Model: AOBH27CMTA
Height difference H
1
*
H
Outdoor unit
5
7.5
30
20
10
7.5
0.988
5
0.992
0.992
0
1.000
1.000
-5
1.000
1.000
-7.5
1.000
-10
-20
30
- 46 -
Indoor unit is lower than outdoor unit
Outdoor unit
H
Indoor unit
Connection pipe
Pipe length (m)
10
20
30
0.930
0.953
0.947
0.981
0.968
0.963
0.985
0.972
0.966
0.989
0.976
0.970
0.997
0.984
0.978
0.997
0.984
0.978
0.997
0.984
0.978
0.997
0.984
0.978
0.984
0.978
0.978

6. Capacity compensation rate for pipe length and height difference

2
*
40
50
0.926
0.921
0.941
0.936
0.956
0.951
0.960
0.954
0.964
0.958
0.972
0.966
0.972
0.966
0.972
0.966
0.972
0.966
0.972
0.966
0.972
0.966