Capacity Compensation Rate For Pipe Length And Height Difference; Model: Aohg09Kvcbn - Fujitsu GENERAL AGHG09KVCB Design & Technical Manual

Hide thumbs Also See for GENERAL AGHG09KVCB:
Table of Contents

Advertisement

6. Capacity compensation rate for pipe length and height
difference
Indoor unit is higher than outdoor unit
Indoor unit
Connection pipe

6-1. Model: AOHG09KVCBN

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than
outdoor unit *2
HEATING
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than
outdoor unit *2
6-1. Model: AOHG09KVCBN
Height difference H
1
*
H
Outdoor unit
5
15
10
7.5
5
0.992
0
1.000
-5
1.000
-7.5
-10
-15
5
15
10
7.5
5
1.000
0
1.000
-5
0.995
-7.5
-10
-15
- 46 -
Indoor unit is lower than outdoor unit
Outdoor unit
H
Indoor unit
Connection pipe
Pipe length (m)
7.5
10
0.955
0.975
0.959
0.979
0.963
0.987
0.970
0.987
0.970
0.987
0.970
0.970
Pipe length (m)
7.5
10
1.004
1.013
1.004
1.013
1.004
1.013
1.004
1.008
0.999
1.005
0.997
0.994

6. Capacity compensation rate for pipe length and height difference

2
*
15
20
0.893
0.909
0.908
0.924
0.912
0.928
0.916
0.931
0.923
0.939
0.923
0.939
0.923
0.939
0.923
0.939
0.923
0.939
15
20
0.956
0.938
0.956
0.938
0.956
0.938
0.956
0.938
0.956
0.938
0.951
0.933
0.948
0.931
0.946
0.929
0.937
0.919