COMPLETION OF ADDRESS SETTING MODE
13) Press the three buttons of SET TEMP. p, SET TEMP. q and FAN at the same time
for 5 seconds or longer. The address setting mode will be cleared and the regular
display will be restored.
*
If no key entry is made for 60 seconds, even though none of the above buttons is
pressed, the address setting mode will automatically be cleared.
(If the address setting mode is automatically cleared while setting addresses,
activate the mode again according to the procedure in step 4) above.)
SETTING UP EACH INDOOR UNIT
01
Simple remote
controller
Repeat the procedures in steps 1) through 13), and set up the indoor units
requiring address setting.
RESET THE POWER AFTER SETTING UP ADDRESS OF ALL
INDOOR UNITS
Important
*
If the reset is not performed, address can not be read in normally6
*
After all the addresses have been set, the circuit breaker needs to be switched off
for at least 2 minutes6
After the 2 minutes has passed, power can be restored6
*
The set address is stored in the PCB and will remain in memory even when the
power is turned off6
However setting address is effective after power reset6
Record the address set in the indoor unit on a label, etc., and affix the label to the
unit so it can be used for after6sales service operations6
Indoor unit
Indoor unit
Indoor unit
00
0
01
01
1
01
02
- (06 - 94) -
Normal mode display
Indoor unit
2
01
13
0
Simple remote
Simple remote
controller
controller
Indoor unit
Indoor unit
01
14
1
01
15
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents