Capacity Compensation Rate For Pipe Length And Height Difference; Model: Aobg18Kmca - Fujitsu ASBG18KMBA Design & Technical Manual

Table of Contents

Advertisement

6. Capacity compensation rate for pipe length and height
difference
Indoor unit is higher than outdoor unit
Indoor unit
Connection pipe

6-1. Model: AOBG18KMCA

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than outdoor
unit *2
HEATING
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than outdoor
unit *2
6-1. Model: AOBG18KMCA
Height difference H
1
*
H
Outdoor unit
5
15
10
7.5
5
0.992
0
1.000
-5
1.000
-7.5
-10
-15
5
15
10
7.5
5
1.000
0
1.000
-5
0.995
-7.5
-10
-15
- 42 -
Indoor unit is lower than outdoor unit
Outdoor unit
H
Indoor unit
Connection pipe
Pipe length (m)
7.5
10
0.929
0.960
0.933
0.964
0.937
0.972
0.944
0.972
0.944
0.972
0.944
0.944
Pipe length (m)
7.5
10
0.968
0.994
0.968
0.994
0.968
0.994
0.968
0.989
0.963
0.987
0.961
0.959

6. Capacity compensation rate for pipe length and height difference

2
*
15
20
0.858
0.868
0.872
0.882
0.876
0.885
0.879
0.889
0.887
0.896
0.887
0.896
0.887
0.896
0.887
0.896
0.887
0.896
15
20
0.896
0.879
0.890
0.879
0.896
0.879
0.896
0.879
0.896
0.879
0.891
0.875
0.889
0.873
0.887
0.871
0.878
0.862