Electrical Connection; Equipotential Bonding - Miele PW 6241 Operating And Installation Instructions

Commercial washing machine
Table of Contents

Advertisement

Installation
Versions:
66

Electrical connection

The electrical connection must only be carried out by a suitably quali-
fied electrician in accordance with local and national regulations.
When installing a residual current device (RCD), it must be Type B.
The electrical components of the machine PW 6241, PW 6321 com-
ply with local codes.
Connection terminals are located behind a cover.
The machine is supplied ex-works for 3N AC 50–60 Hz. The voltage is
stated on the data plate.
3 AC 208 V 60 Hz
3 AC 440 V 60 Hz
2 AC 208 V 60 Hz
For hard-wired machines, an all-pole means of deactivation must be
provided on site. Switches with a minimum contact gap greater than
1/8" (3 mm) are suitable disconnectors. These include C/B, fuses,
and contactors (VDE 0660).
The plug connector or disconnector must be easily accessible at all
times.
If the machine is disconnected from the power supply, the discon-
nector must be lockable or the point of disconnection must be moni-
tored at all times.

Equipotential bonding

An equipotential bond with good contact connection must always
be provided in accordance with all national and local regulations.
The electric heating is set ex-works to 24 kW (PW 6241), 30 kW
(PW 6321).
The minimum liquor level to activate the heater is 4 5/16" ( ) water col-
umn.
The motor is protected against overload by winding protection.
3 AC 220-240 V 60 Hz
3 AC 480 V 60 Hz
2 AC 220-240 V 60 Hz