3.2.5.2 Bottom Cable Routing

Context
● If you choose to route cables from the bottom of the cabinet, ensure sufficient
● If cables need to be routed through holes, remove cable covers for power
● This section describes cable connections when the mains input and bypass
● The figures are for reference only. For more information about the
Procedure
Step 1 Open the front door of the bypass cabinet, and remove the covers of the power
distribution subrack from the bypass cabinet.
Step 2 Remove the cable covers from the bottom of the cabinet, drill holes in the covers,
attach grommet strips to the hole edges for protecting cables, and reinstall the
cable covers.
The hole size and quantity are for reference only.
Issue 07 (2022-06-20)
NO TICE
space at the bottom of the cabinet.
cables from the bypass cabinet and drill holes in the covers. After drilling holes,
attach grommet strips on the hole edges for protecting cables. Reinstall the
covers on the cabinet.
input use different power sources. When they use the same power source, there
is no need to remove the copper bars between the mains and bypass input
terminals or connect the bypass input power cable.
recommended cable cross-sectional area and quantity, refer to
Power Cables
and site requirements.
NO TE
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Installation
3.1.3 Preparing
81