UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
Figure 3-7 Expansion bolt composition
(1) M12 bolt
(4) Expansion sleeve
Step 3 Use a pallet truck to move the cabinet to the installation position.
Step 4 Use M12x60 expansion bolts to secure the cabinet to the expansion bolt mounting
holes on the floor.
Figure 3-8 Tightening expansion bolts
Step 5 Install the front, rear, left, and right anchor baffle plates.
Issue 07 (2022-06-20)
Copyright © Huawei Digital Power Technologies Co., Ltd.
(2) Spring washer
(5) Expansion nut
3 Installation
(3) Flat washer
(6) Concrete floor