7.3 Environmental Specifications

Table 7-3 Environmental specifications
Item
Operating
temperature
Storage
temperature
Humidity
Altitude
Issue 07 (2022-06-20)
Maintenance
Bypass
Switch
1000 V
AC/630 A/3P
1000 V
AC/800 A/3P
1000 V
AC/800 A/3P
1000 V AC/
1000 A/3P
1000 V AC/
1000 A/3P
Specifications
0–40°C
–40°C to +70°C
0%–95% RH (non-condensing)
0–1000 m
When the altitude is higher than 1000 m, the power is
derated as described in IEC 62040-3. The upper limit of the
altitude is 4000 m.
NO TE
When the altitude ranges from 3000 m to 4000 m, the maximum operating temperature is
30°C.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Mains Input
Bypass Input
Switch
Switch
1000 V
1000 V
AC/800 A/3P
AC/630 A/3P
-
-
1000 V AC/
1000 V
1000 A/3P
AC/800 A/3P
-
-
1000 V AC/
1000 V AC/
1250 A/3P
1000 A/3P
7 Technical Specifications
Output
Switch
1000 V
AC/630 A/3P
-
1000 V
AC/800 A/3P
-
1000 V AC/
1000 A/3P