Appendix A Specifications
A.1 General Specifications
Item
Operating ambient temperature
Storage temperature
Operating ambient relative
humidity
Dust
Degree of contamination
Corrosive gas
Usable altitude
Vibration resistance
(vibration immunity)
Shock resistance
(shock immunity)
Free fall
Noise resistance
First transient
Electrostatic discharge
Radiation field level
Grounding
Structure
Installation location
(Note 1)
For long-term storage, store spare parts in dark places and avoid hot or wet places.
For long-term storage, the temperature and humidity should be 0-40°C and 20-80%RH (no condensation)
respectively, and the temperature variation rate should be less than or equal to 10°C/h.
(Note 2)
The following components shall not be contained
Hydrogen sulfide, sulfurous acid gas, chlorine gas, nitrogen oxides (NOx), sulfur oxides (SOx), ammonia,
silicon gas, and so on.
(Note 3)
Grounding (e.g., mesh grounding) other than Class D grounding can be applied to the system under a
condition which achieves the equivalent effect as with Class D grounding. For grounding other than Class D,
the user shall check for the effect of the grounding.
6F8C1872
40
Table A-1 General Specifications
Specifications
0 to 55°C, 24-hour average temperature 40°C or less
-40°C ~ +70°C
10 to 95%RH, level RH2 (no condensation)
Dust 0.3mg/m
3
(no conductive dust)
2 (usually, no conductive contamination) or less
No corrosive gasses
No silicon-containing substances
Up to 2000m above sea level
IEC 60068-2-6, Test Fc-compliant
5  f < 8.4Hz
: Half amplitude 3.5mm
8.4  f < 150Hz : Constant acceleration 9.8m/sec
IEC 60068-2-27, test Ea-compliant
147m/s
(15G)
2
X, Y, Z direction, 3 cycles each
Shipping package: 1,000mm
Product package: 300mm
I/O power supply, Signal line
4kV (contact discharge), level ESD-3
10 V/m
Class D grounding
Open-type equipment
Inside of indoor control panel
Remarks
(Note 1)
IEC 61131-2
(Note 2)
2
IEC 61000-4-4
IEC 61000-4-2
IEC 61000-4-3
(Note 3)

Hide quick links: