Chapter 2 Name and Function of Module Components
Mode 2 setup switch (binary DIP switch)
Used to set the action when there is a controller error or transmission error.
Set to "OFF" at shipment.
Mode
Halt1
Halt2
Resume1
Resume2
CE: Controller Error TE: Transmission Error
Address setup switch (decimal rotary switch)
Use to set the slave's node address (1 to 99). Set to "1" at shipment.
NAx10 : 10's digit (module lower side)
NAx1 : 1's digit (module upper side)
Cutout side
The above figure is set to node address "00". (Actual setting should be between 1 and 99.)
Align the notch side of the knob with the desired value.
6F8C1872
12
Table 2-4 Mode 2 setup switch
MD4 MD5 Data update Abnormal
OFF
OFF
Halt
OFF
ON
halt
ON
OFF
Resume
ON
ON
Resume
Figure 2-5 Node address setting
Transmit data
CE
---
TE
---
CE
---
TE
---
Value just before
CE
error
TE
---
CE
0
TE
---
Cutout side
Cutout side
Receive data
---
Value just before error
---
0
Data received from master
Value just before error
Data received from master
0
NAx1
NAx10