Hunting/Surging - Kohler 6VSG Service Manual

Dc generator sets
Hide thumbs Also See for 6VSG:
Table of Contents

Advertisement

• Check for electronic governor faults.
shutoff solenoid deenergizes and the generator set
shuts down under the following conditions:
Closed throttle
Engine overspeed
Broken fuel shutoff solenoid lead
Broken stepper motor leads (erratic
performance)
Failed actuator linkage (erratic performance)
• Check the fuel supply pressure and the fuel supply
system for leaks, blockages, and/or failed system
components (regulators, valves, etc.). See Section
5.8, Fuel Systems.
5.6.3

Hunting/Surging

Hunting/surging problems thought to be caused by the
governor system are more likely to be caused by fuel
supply, engine, or carburetor problems. Check engine
speed stability using the following procedure before
testing the governor.
!
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set
until it cools.
Servicing the exhaust system.
severe injury or death. Do not touch hot engine parts. The
engine and exhaust system components become extremely
hot during operation.
1. Open the generator set line circuit breaker.
2. Start the generator set.
3. Hold the throttle linkage steady while the engine
is running. See Figure 5-13. If the engine runs at
a steady speed with no hunting or surging when
the
throttle
is
hunting/surging problems during operation may
be caused by the governor. Proceed to Section
5.6.4.
4. Check the linkage between the stepper motor
and the carburetor.
damaged components.
5. Verify that the speed control parameters have not
been modified.
Governor setting to the default setting.
Figure 5-16.
72
Section 5 Component Testing and Adjustment
The fuel
WARNING
Hot parts can cause
held
steady,
then
Replace any worn or
Reset the Engine Speed
6. If the engine speed hunts or surges while the
throttle is held steady, check the carburetor and
engine operation. Refer to the engine service
manual for engine diagnostic and service
information.
Figure 5-13
1
1. Electronic governor stepper motor
2. Carburetor throttle linkage
3. Carburetor
Figure 5-13 Stepper Motor and Carburetor
the
See
2
3
TP-6844 1/13
KPS_096

Advertisement

Table of Contents
loading

Table of Contents