Figure 3-4
Genset
---->
System
* If the exerciser has not been set,
No Exercise Sch will be displayed.
Figure 3-4
Genset System Menu
TP-6844 1/13
System Voltage:
54.0 V
Auto Start Volt:
50 V
Auto Stop Load:
40 %
Pct. Load Limit:
100 %
Fuel Type:
Natural Gas
*
Next Exercise:
01:00p 02Dec2012
Exercise Mode:
Loaded Full Sp
Exercise Freq:
Weekly
Meas System:
English
Contrast:
50
<----
Return
tp6804
System Voltage: The system voltage is the output
voltage of the generator set. Default values are shown
in Figure 3-5.
The system voltage is set to the
required output voltage to properly support the load
and charge the battery. Do not confuse this value with
the voltage designation of the battery stack.
example, four 12V batteries in series results in a 48V
battery stack, but the output voltage needed to charge
the battery stack is 54V.
Figure 3-5
Nominal Voltage
Default System Voltage, VDC
Figure 3-5
System Voltage Default Settings
Refer to the battery manufacturer's documentation for
the recommended charging voltage.
voltage needs to be changed, see the Operation
Manual for instructions to change settings.
Note: Setting the system voltage to a higher value
than the factory default setting will decrease the
power output of the generator set.
A 6VSG set at the system voltage shown in Figure 3-5
will have an output of 6 kW. If the system voltage is
set to a higher value, the output current decreases.
The available power output also decreases below 6
kW due to the limits on the engine speed. The graphs
in Figure 3-7 illustrate the effect of changing the
system voltage.
Auto Start Volt: The 6VSG will automatically start
when the battery bank voltage has reached or fallen
below this value for 180 seconds (3 minutes). Default
settings are shown in Figure 3-6.
Figure 3-6
Nominal Voltage
Default Auto Start Voltage, VDC
Figure 3-6
Auto Start Voltage
Note: The 3-minute (180-second) time delay can be
changed using a personal computer (laptop)
®
and Kohler
SiteTech
3-9 for SiteTech parameters.
For
24V
36V
48V
27
40.5
54
If the system
24V
36V
48V
25
37.5
50
software. See Figure
Section 3 Controller
29