Fault Message
Fuel Spill *
Gen Running
Low Fuel *
Minor Fault
Rmt StartCmd
(Remote Start Command Issued)
Run Btn Ack
(Run Button Acknowledged)
Start Delay
(Engine Start Delay Active)
System Ready
VSpdStartCmd (Variable Speed
Start Command)
* Programmable Interface Module (PIM) required.
Figure 4-3 Status Messages Displayed on the VSC Controller
56
Section 4 Troubleshooting
Action
Description/Comments
Notice
The digital output for Fuel Spill (PIM) is
active (contacts closed), indicating any of
the digital inputs for Fuel Tank Leak
Warning, Fuel Tank Leak Shutdown,
Engine Fuel Level Warning or Engine
Fuel Level Critically High (PIM) is active
(low).
Notice
The digital output for Generator Running
(PIM) is active (contacts closed),
indicating the generator is running.
Notice
The digital output for Low Fuel (PIM) is
active (contacts closed), indicating any of
the digital inputs for Low Fuel Pressure
Warning, Low Fuel Level Warning or Low
Fuel Level Shutdown (PIM) is active
(low).
Notice
The digital output for Minor Fault (PIM) is
active (contacts closed), indicating either
the digital input for Ground Fault Indicator
Warning (PIM) is active (low) or the
controller detected Low Cranking
Voltage.
Notice
The controller has received a remote start
signal while the master switch is in AUTO,
and will go to normal running.
Notice
The RUN button on the controller has
been pushed.
Notice
The digital output for Engine Start Delay
(PIM) is active (contacts closed),
indicating the engine is in between active
cranking cycles.
Notice
The digital output for System Ready
(PIM) is active (contacts closed),
indicating the generator has no active
faults or warnings.
Notice
A diagnostic exercise request has been
received by the controller.
Check
Check customer equipment
connected to the PIM module.
Check controller front panel
buttons for potential RUN
command. If in AUTO, check
remote start lines.
Check customer equipment
connected to the PIM module.
Check customer equipment
connected to the PIM module.
Check cranking battery
condition.
Verify remote start signal.
NA
NA
NA
Check for a remote exercise
command from OnCue.
TP-6844 1/13